3 exchange the electronics – KROHNE OPTISWITCH 3300C Transistor EN User Manual
Page 24
l
Wrong mode selected
à
Set the correct mode on the mode switch (max.: overfill
protection; min.: dry run protection). Wiring should be
carried out according to the quiescent current principle.
?
Signal lamp flashes red
l
Electronics has detected a failure
à
Exchange instrument or return instrument for repair
7.3 Exchange the electronics
In general, all oscillators of series WE60 can be interchanged.
If you want to use an oscillator with a different signal output,
you can download the corresponding operating instructions
manual from our homepage under Downloads.
With EEx d instruments, the housing cover must only be
opened if there is no explosive atmosphere.
Proceed as follows:
1 Switch off power supply
2 Unscrew the housing cover
3 Lift the opening levers of the terminals with a screwdriver
4 Pull the connection cables out of the terminals
5 Loosen the two screws with a screw driver (Torx size T10
or slot 4)
2
1
Fig. 15: Loosen the screws
1
Electronics module
2
Screws (2 pcs.)
24
OPTISWITCH 3300 C - with transistor output
Maintenance and fault rectification
29962
-EN
-060830