3 function chart, Green = relay energized, Red = relay deenergized – KROHNE OPTISWITCH 5100C Relay EN User Manual

Page 19

Advertising
background image

Control lamp (LED) for indication of the switching condition

l

green = relay energized

l

red = relay deenergized

l

red (flashing) = failure

With the mode adjustment (A/B) you can change the switching

condition of the relay. You can set the required mode acc. to

the "Function chart" (A - max. detection or overfill protection, B

- min. detection or dry run protection).

With this DIL switch (3) you can set the switching point to

liquids having a density between 0.5 and 0.7 g/cm³ (0.018 and

0.025 lbs/in³). With the basic setting, liquids with a density of

>0.7 g/cm³ (>0.025 lbs/in³) can be detected. In liquids with

lower density, you must set the switch to >0.5 g/cm³

(>0.018 lbs/in³). The specifications for the position of the

switching point relate to water - density value 1.0 g/cm³

(0.036 lbs/in³). In products with a different density, the

switching point will shift in the direction of the housing or tuning

fork end depending on the density and type of installation.

6.3 Function chart

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Level

Switching status

Control lamp

Mode A

Overfill protection

5

3

4

(8)

(6) (7)

Relay energized

Green

Mode A

Overfill protection

5

3

4

(8)

(6) (7)

Relay deenergized

red

Mode B

Dry run protection

5

3

4

(8)

(6) (7)

Relay energized

Green

Mode B

Dry run protection

5

3

4

(8)

(6) (7)

Relay deenergized

red

Signal lamp (1)

Mode adjustment (2)

Sensitivity adjustment (3)

OPTISWITCH 5100 C, 5150 C - with relay output

19