4 Mounting

4.1 General instructions

In general, OPTISWITCH 5200 C, 5250 C can be mounted in

any position. The instrument must be mounted in such a way

that the tuning fork is at the height of the requested switching

point.
The tuning fork has lateral markings (notches), marking the

switching point with vertical mounting. The switching point

refers to water with the basic setting of the sensitivity switch

>=0.7 g/cm³ (>=0.025 lbs/in³). When mounting OPTISWITCH

5200 C, 5250 C, make sure that this marking is at the height of

the requested switching point. Keep in mind that the switching

point of the instrument is shifted if the medium has a density

other than water - water =1 g/cm³ (=0.036 lbs/in³). For

products <0.7 g/cm³ (<0.025 lbs/in³) and >0.5 g/cm³

(>0.018 lbs/in³) the density switch must be set to >=0.5 g/cm³.

2

3

1

4

Fig. 2: Vertical mounting

1

Switching point approx. 13 mm (approx. 0.51 in)

2

Switching point with lower density

3

Switching point with higher density

4

Switching point approx. 27 mm (approx. 1.06 in)

Switching point

10

OPTISWITCH 5200 C, 5250 C - with contactless electronic switch

Mounting

30433

-EN
-060831