Operation

5.1 HART

®

networks

5.1.1 Point-to-point connection analog / digital mode

Point-to-point connection between the transmitter and the HART

®

master.

The current output of the device may be active or passive.

DANGER!
Only connect an Ex approved HART

®

modem located in a safe area to a transmitter in a

potentially explosive area.

CAUTION!
In order to ensure reliable HART

®

communication with this transmitter, the loop resistance

must be at least 250 Ω!

1 Primary Master
2 HART

®

modem

3 HART

®

signal

4 Analog indicator
5 Terminal 5
6 Terminal 6
7 Device with address = 0 and passive or active current output
8 Secondary Master
9 Power supply for devices (slaves) with passive current output
10 Load ≥ 250 Ω (Ohm)