10 supplement, 1 technical data – KROHNE SU 501 EX EN User Manual

Page 31

Advertising
background image

10 Supplement

10.1 Technical data

General data
Series

module unit with plug-in socket for mounting on

carrier rail 35x7.5 or 35x5 acc. to EN 50022

Dimensions

W = 36 mm (1.42 in), H = 118.5 mm (4.66 in), D

= 134 mm (5.28 in)

Weight

approx. 170 g (6 oz)

Housing material

Noryl SE100, Lexan 920A

Socket material

Noryl SE100, Noryl SE1 GFN3

Screw terminals

max. 1x1.5 mm²

Power supply
Power supply

20 … 250 V AC, 50/60 Hz, 20 … 72 V DC

Power consumption

max. 3 W (3 … 18 VA)

Sensor input
Quantity

1

Data transmission

Analogue

Hysteresis

100 µA

Switching threshold

12 mA

Current limitation

24 mA (permanently short-circuit proof)

Sensor power supply

15 … 18 V DC

Detection line break

<=3.6 mA

Detection shortcircuit

>=21 mA

Connection cable

2-wire

Resistance per conductor

max. 35 Ohm

Relay output
Number, function

1x switching relay (spdt)

Integration time

0.2 … 20 s, directional switching

Mode

A/B switch (A - max. detection or overfill

protection; B - min. detection or dry run

protection)

Contact

1x spdt

Contact material

AgNi, hard gold-plated

Turn-on voltage

min. 10 mV DC, max. 250 V AC, 250 V DC

Switching current

min. 10 µA DC, max. 3 A AC, 1 A DC

Breaking capacitance

max. 500 VA, max. 54 W DC

SU 501 Ex - Signal conditioning instrument

31

Supplement

27953

-EN

-050616

Advertising