Modbus protocol – KROHNE GFC 300 Modbus User Manual
Page 13
MODBUS PROTOCOL
6
13
GFC 300
www.krohne.com
03/2012 - 7312402100 - AD Modbus GFC 300 R01 en
Modbus protocol
address
Description and settings
Type
Number of registers
1st
2nd
30000
0
Volume flow
float
2
30002
2
Corrected volume flow (gas only)
float
2
Enthalpy flow (steam only)
30004
4
Mass flow
float
2
30006
6
Molar mass (gas only)
float
2
Specific enthalpy (steam only)
30008
8
Not used, returns zero (gas only)
float
2
Density (steam only)
30010
10
Flow speed
float
2
30012
12
Velocity of sound
float
2
30014
14
Gain
float
2
30016
16
Diagnostics 1
value 2436.32
1 = none
2 = velocity of sound 1
3 = gain 1
4 = SNR 1
float
2
30018
18
Diagnostics 2
value 2437.32
1 = none
2 = velocity of sound 2
3 = gain 2
4 = SNR 2
float
2
30020
20
Diagnostics 3
value 2438.32
1 = none
2 = velocity of sound 3
3 = gain 3
4 = SNR 3
float
2
30022
22
Temperature of the medium
(only with appropriate Current Input)
float
2
30024
24
Pressure of the medium
(only with appropriate Current Input)
float
2
30026
26
Operating time
float
2
30028
28
counter 1
double float 4
30032
32
Counter 2
double float 4
30036
36
Counter 3 (IO2 only)
double float 4
30040
40
Long status sensor
byte [4]
2
30042
42
Long status device
byte [4]
2