MODBUS PROTOCOL

24

MFC 400

www.krohne.com

05/2013 - 4002525102 - AD Modbus MFC 400 R02 en

5.8.13 Modbus RS485 Communication Settings

34046

34046

34046

34046

(0x84FE)

CF27

Float

2

D1.1.25

34500

34500

34500

34500

(0x86C4)

CF25

Byte

1

D1.1.23

Modbus Function Codes "Read Holding Registers" (0x03) and "Write Multiple Registers" (0x10)

Holding
Register

Name

Description

Type

No. of
registers

Values

Display
Fct. No.

50000

50000

50000

50000

(0xC350)

Baud rate

Baud rate for the RS485

Modbus Communication in

[bps]

Long

2

1200, 2400, 3600,

4800, 9600, 19200

(default), 38400,

57600, 115200

C6.8.2

50002

50002

50002

50002

(0xC352)

Transmission

Delay

Select transmission delay

between Modbus request and

Modbus response in [ms]

Float

2

0 (default)...0.04

C6.8.5

50004

50004

50004

50004

(0xC354)

Slave Address

Modbus Slave Address

Byte

1

1 (default)...247

C6.8.1

50005

50005

50005

50005

(0xC355)

Parity

Parity for the RS485 Modbus

Communication

Byte

1

0 = Even (default)

1 = Odd

3 = Off

C6.8.3

50006

50006

50006

50006

(0xC356)

Register

Format

Switch Register Format Little

Endian or Big Endian

Byte

1

0 = Little Endian

1 = Big Endian

(default)

C6.8.4

50007

50007

50007

50007

(0xC357)

Stop Bits

Number of Stop Bits

Byte

1

1 = 1 Stop Bit

(default)

2 = 2 Stop Bits

C6.8.6

Modbus Function Code "Read Input Registers" (0x04)

Input
Register

Name

Type

No. of registers

Display
Fct. No.