Technical data: level transmitter modules

Name

PRETOP 5343B

PR 5350B

PR 5335B

Description


4 … 20mA. Conversion of
resistance variation to
analogue current signals.

PROFIBUS PA or FF.
Conversion of resistance
variation.

4-20mA+HART

®

.

Conversion of resistance
variation to analogue
current signals.
Connection of up to 15
transmitters to a digital 2-
wire signal with HART
communication.

Output

4 … 20 mA
(limits : 3.5 & 23 mA)

PROFIBUS

®

PA protocol

Profile A&B, ver. 3.0 (EN
50170 vol.2) or
FOUNDATION™
Fieldbus protocol

4 … 20 mA
(limits : 3.5 & 23 mA) and
HART

®

protocol (loop link)

Max. load R

L

(U – 8) Ohms
0.023

-

(U – 8) Ohms
0.023

Measuring
error


± 10 mm

Power supply 8 … 35Vdc

8 … 30Vdc (ATEX)

9 … 32Vdc
9 … 30Vdc (ATEX)

8 … 35Vdc
8 … 30Vdc (ATEX)

Ambient
temperature


Refer to table in “ATEX applications: special conditions for safe use”, section 7.1

Approvals
Ex

EEx ia, EEx d

Max power
dissipated by
Exd housing,
P

max



5 W

Max voltage
for Exd
housing, U

max


36 V

Max safety
values for Exi
applications


U

i


28V


30 V


28V

I

i

120mA

120mA

120mA

P

i

0.84W

0.84W

0.84W

C

i

1nF

2nF

1nF

Terminal
block

L

i

10µH

1µH

10µH