START-UP

50

OPTIBAR DP 7060 C

www.krohne.com

04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en

5.4.4 Additional adjustments

PIN

In this menu item the PIN can be changed. This option is only available if it has been enabled under

"Setup - Lock adjustment". The PIN is "0000" by default factory conditions.

0000

Change PIN

Date / Time

Internal clock setting

Write date, time, data in device

Reset

For further information refer to

Reset on page 51.

Factory settings, Basic settings, Totalizer 1 and Totalizer 2

Copy instrument

settings

For further information refer to

Saving the device settings on page 52.

Copy instrument settings

Special

parameters

Changing these settings is possible only after consultation with a service employee.

Scaling

In menu item "Scaling variable" you define the scaling variables and the scaling unit for the level

mode.

In menu item "Scaling format" you define the scaling format on the display and the scaling of the

level measurement for 0% and 100%.

Scaling variable

Scaling variable

Scaling unit

Scaling format

Scaling format

100% corresponds - user-defined value

0% corresponds - user-defined value

Current output

In this menu item it is determined which measured variable relates to which current output. Under

"Current output - Adjustment", the current output can be assigned a corresponding measured

value.

Current output

variable

For applications "Level"

Filling height or Pressure (Adjustment units), Static pressure, Percent,

Scaled, Linear percent, Meas. cell temp. and Electronics temperature

For applications "Differential pressure"

Differential pressure, Static pressure, Percent, Linear percent, Meas. cell

temp. and Electronics temperature

For applications "Flow"

Flow, Differential pressure, Static pressure, Pressure, Percent, Scaled,

Linear percent, Meas. cell temp. and Electronics temperature

For applications "Interface"

Interface height, Differential pressure, Percent, Scaled, Linear percent,

Meas. cell temp. and Electronics temperature

For applications "Density"

Density, Differential pressure, Percent, Scaled, Linear percent, Meas. cell

temp. and Electronics temperature

Current output,

adjustment

0% = 0% or 100% = 100%

HART

®

-Mode

The differential pressure transmitter offers the HART

®

modes "Analogue current output" and "Fix

current (4 mA). Under "Fix current (4 mA)", up to 64 sensors can be operated on a two-wire
multidrop mode. Each device must be assigned a HART

®

address between 0 und 63. The analogue

signal is fixed at 4 mA. Under "Analogue current output", however, a 4…20 mA signal can also be
issued for the assigned HART

®

address in multidrop mode.

HART

®

address

0...63

Output mode

Analogue current output with HART

®

or Fix current (4 mA) with HART

®