KROHNE ALTOFLUX 2W IFM 4042K EN User Manual

Page 24

Advertising
background image

Section 4.4

Part B IFC 040 Signal converter

ALTOFLUX 2W

02/2001

24

Display texts

Description and settings

FCt. 1.5

CURRENT OUTPUT

Current output
For characteristic, see Fig. 2 in Section 2.3

For HART function “No" or

address “0"

Settings for the current output
Not possible when ”Address 1 –15” is set under Fct. 3.6
HART (equivalent to multidrop mode).
In that case, only a constant current needs to be set,
see Fct. 3.6 HART “I Multidrop".
Fct. 1.5 Current output then has “no function".

inFo

Function

Edit

off

PoS.direction
neG.direction

abSolute

neG-0-PoS

Standard: absolute

Setting the characteristic of the current output
“off” = 0 per cent current output

Please note:
Fct. 1.7 Status output, “Automatic range change" setting.

inFo

0 Perc.current

0 per cent current

XX.X

mA

Range 4.0 ... 14.0mA

Standard: 4.0 mA

Setting of current at “zero” flow(I

0%

)

inFo

100 Perc.current

100 per cent current

XX.X

mA

Range 10.0 ... 20.0 mA

I

0%

< I

100%

Standard: 20 mA

Setting of current at 100 % flow (I

100%

),

according to the full-scale range (Q

100%

)

under Fct. 1.1 Full Scale.

inFo

error current

Fault current

XX.X

mA

Range 3.6 ... 22.4 mA

I

Error

< I

0%

or I

100%

< I

Error

Standard: 22 mA

The fault current that is output in the event of a fault.

Please note:
When the current output is overranged, the maximum current
is 21mA and has been preset by factory.

Advertising