Connect communication cables between the ups and, Battery enclosure – APC MGE 300 User Manual

Page 11

Advertising
background image

7

MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation

Connect Communication Cables between the UPS

and Battery Enclosure

External battery temperature (ATIZ) and external battery breaker signal

Note: The ATIZ cable is for external battery temperature detection signal (cable is pre-
installed).

Note: The battery cable is for external battery breaker signal (cable is pre-installed).

Note: The connection of communication cables is only applicable between the UPS and XR1.
For the connection of XR2, follow step 2 only.

1. Run

the

combined

battery breaker and
ATIZ signal

cable from

the XR connection
terminal as shown.
Note! See the UPS
installation manual for
information on where
to connect the other
end of the cable(s) to
the UPS.

2. Run the four cables

from the XR
connection terminal to
the XR battery breaker
(see the below table for
cable description).

Cable description (step 2)

Cable color

Cable label

Description

Yellow

QB OF-11

CB contactor signal

White

QB OF-14

CB contactor signal

Red

QB OF-D4

+12 V power supply

Black

QB OF-D1

-12 V power supply

Front view

Battery breaker signal

cable to the UPS

To the UPS

Battery

enclosure