Start Learning the Process. After the
process has been learned the menu
item will revert to no.

no

Learning will stay in present mode.

dFAC

Damping factor, Select OFF, 1 to 7. Sets the ratio
of Rate to Reset for the SELF tunE mode. 7 =
most Rate. Factory set to 3. For a fast response
process the value should be lowered (less Rate).
For a slower process the value should be in-
creased (more Rate).

Pid

Manually adjust the PID values. PID control consists of
three basic parameters, Proportional Band (Gain), Reset
Time (Integral), and Rate Time (Derivative).

#Pb1

(Option 948, 4-Stage Set Point) or

Pb1

Proportional Band (Bandwidth). Select 1 to 9999
°F, °C, or counts.

Pb2

Proportional Band (Bandwidth). Select 1 to 9999
°F, °C, or counts. Appears only if control is
equipped with second set point and Out2 is NOT
selected as ONOF.

#rES

(Option 948, 4-Stage Set Point) or

rES

Automatic Reset Time. Select OFF, 0.1 to 99.9
minutes. Select OFF to switch to OFS.

#OFS

(Option 948, 4-Stage Set Point) or

OFS Manual Offset Correction Select OFF, 0.1 to 99.9%.

Select OFF to switch to rES.

#rtE

(Option 948, 4-Stage Set Point) or

rtE

Rate Time. Select OFF, 0.01 to 99.99 minutes,
Derivative.

SLO

PID values are preset for a slow response process.

nor

PID values are preset for a normal response process.

FASt

PID values are preset for a fast response process.

Pid2

Linkage of PID parameters between SP1 and SP2: Select On or

OFF.
On

Applies SP1 rEs, rtE, Fbnd, and FrtE terms to SP2 for
heat/cool applications.

OFF

SP2 functions without rEs, rtE, Fbnd and FrtE.

ArUP

Anti- Reset Windup Feature: Select On or OFF.
On

When ArUP is On the accumulated Reset Offset value
will be cleared to 0% when the process input is not within
the Proportional Band.

OFF

When ArUP is OFF, the accumulated Reset Offset
Value is retained in memory when the process input is