Address Content

Explanation

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1027H

Lower-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1028H

Upper-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

1029H

Lower-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

102AH

Read LED status

b0 : Alm3, b1: Alm2, b2: F, b3: _, b4: Alm1, b5: OUT2, b6:
OUT1, b7: AT

102BH

Read push button status

b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push

102CH

Setting lock status

0 : Normal, 1 : All setting lock, 11 : Lock others than SV value

102FH

Software version

V1.00 indicates 0x100

1030H

Start pattern number

0 ~ 7

1040H~

Actual step number setting inside the

0 ~ 7 = N, indicate that this pattern is executed from step 0 to

1047H

correspond pattern step N

1050H~

Cycle number for repeating the execution of 0 ~ 99 indicate that this pattern has been executed for 1~100

1057H

the correspond pattern

times

1060H~

Link pattern number setting of the

0 ~ 8, 8 indicates the program end. 0~7 indicates the next

1067H

correspond pattern

execution pattern number after executing the current pattern

2000H~

Pattern 0~7 temperature set point setting

-999 ~ 9999

203FH

Pattern 0 temperature is set to
2000H~2007H

2080H~

Pattern 0~7 execution time setting

Time 0 ~ 900 (1 minute per scale)

20BFH

Pattern 0 time is set to 2080H~2087H

6.

Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data =

FF00H for bit set, 0000H for bit clear)

Page 25

Address Content

Explanation

0810H

Communication write-in selection

Communication write in disabled: 0 (default), Communication
write in enabled: 1

0811H

Temperature unit display selection

oC / linear input (default) : 1 , oF : 0

0812H

Decimal point position selection

Except for the thermocouple B, S, R type, all the other
thermocouple type are valid. (0 or 1)

0813H

AT setting

OFF: 0 (default), ON : 1

0814H

Control RUN/STOP setting

0 : STOP, 1 : RUN (default)

0815H

STOP setting for PID program control

0: RUN (default), 1: STOP

0816H

Temporarily STOP for PID program control 0: RUN (default), 1: Temporarily STOP