Dwyer TSS2 User Manual

Page 2

Advertising
background image

List of parameters

Description

Units

Range

SP1

Set Point 1

Degrees

r4 to r6

SP2

Set Point 2

Degrees

r5 to r7

r0

Dependency SP1-SP2

Range

ind/dep

r1

Differential for SP1

Degrees

0.1 to 20.0

r2

Differential for SP2

Degrees

0.1 to 20.0

r3

Band differential

Degrees

0.1 to 20.0

r4

Lowest value for SP1

Degrees

-99.9 to r6

r5

Lowest value for SP2

Degrees

-99.9 to r7

r6

Highest value for SP1

Degrees

r4 to 302

r7

Highest value for SP2

Degrees

r5 to 302

r8

Regulation or operating mode

Range

On1/On2/nEU

A0

Alarm differential

Degrees

0.1 to 20.0

A1

Maximum alarm probe 1 (1)

Degrees

0.1 to 99.9

A2

Maximum alarm probe 2 (2)

Degrees

0.1 to 99.9

A3

Minimum alarm probe 1 (1)

Degrees

0.1 to 99.9

A4

Minimum alarm probe 2 (2)

Degrees

0.1 to 99.9

A5

Alarm verification time

h-m (*)

0.0 to 18.0

A6

Alarm probe 1 selection

Range

AHL/Ano/AH/AL

A7

Alarm probe 2 selection

Range

AHL/Ano/AH/AL

c0

Minimum relay stop time

Minutes

0 to 240

c1

Operation relay 1

Range

dir/inv

c2

Operation relay 2

Range

dir/inv

c3

Default operation relay 1

Range

Opn/Clo

c4

Default operation relay 2

Range

Opn/Clo

P0

Temperature scale selection

Range

ºC/ºF

P1

Calibration of probe 1

Degrees

-20.0 to 20.0

P2

Calibration of probe 2

Degrees

-20.0 to 20.0

P3

Decimal point

Range

no/yes

P4

Probe to be displayed

Range

sd1/sd2

P5

Number of probes

Range

1/2

H0

Reprogramming

Range

0

H1

Keyboard protection

Range

no/yes

H2

Operation LED OUT1

Range

dir/inv

H3

Operation LED OUT2

Range

dir/inv

H4

Address for serial communication

Numeric

0 to 999

H5

Access code to parameters

Numeric

0 to 999

H6

Probe type

Range

Ptc/Ntc

(*)h-m are data in format XX.Y where XX are hours and Y tens of minutes.
(1)referred to set 1.
(2)referred to set 2.

Parameter descriptions
SP1 =
Operation order of relay 1. Specifies the ON/OFF point of relay 1. Variable
between r4 and r6.
SP2 = Operation order of relay 2. Specifies the ON/OFF point of relay 2. Variable
between r5 and r7.
r0 = Dependency between SP1 and SP2. Only for mode ONOFF1
ind = order for relay 2, SP2.
dep = order for relay 2, SP1+SP2.
r1 = Differential or hysteresis for relay 1. Temperature differential between ON/OFF
of relay 1 in ON/OFF control.
r2 = Differential or hysteresis for relay 2. Temperature differential between ON/OFF
of relay 2 in ON/OFF control.
r3 = Band differential. Temperature differential between ON/OFF of relays 1 and 2
in neutral area control. For relay 1 it is added to SP1 and for relay 2 it is subtracted
from SP1.
r4 = Lowest value for SP1.
r5 = Lowest value for SP2.
r6 = Highest value for SP1.
r7 = Highest value for SP2.
r8 = Regulation or operating mode. Selection of the operating mode.
A0 = Alarm differential. It is the temperature differential between the alarm On and
Off cycle.
A1 = Maximum alarm probe1.
A2 = Maximum alarm probe2.

Maximum alarm ON when probe 2 higher than SP2+A2
Maximum alarm OFF when probe 2 lower than SP2+A2-A0.

A3 = Minimum alarm probe1.

Minimum alarm ON when probe 1 lower than SP1-A3
Minimum alarm OFF when probe 1 higher than SP1-A3+A0.

A4 = Minimum alarm probe2.

Minimum alarm ON when probe 2 lower than SP2-A4
Minimum alarm OFF when probe 2 higher than SP2-A4+A0.

A5 = Alarm verification time. Time from the alarm event until it trips.
A6 = Alarm probe 1 selection.

AHL=Maximum and minimum alarm probe 1 enabled.
Ano=No alarms probe 1.
AH=Maximum alarm probe 1 enabled.
AL=Minimum alarm probe 1 enabled.

A7 = Alarm probe 2 selection.

AHL=Maximum and minimum alarm probe 2 enabled.
Ano=No alarms probe 2.
AH=Maximum alarm probe 2 enabled.
AL=Minimum alarm probe 2 enabled.

c0 = Minimum relay stop time. Minimum time from the disconnection of a relay until
it can be switched on again.
c1 = Operation relay 1. Selection between direct or reverse operation for relay 1.
c2 = Operation relay 2. Selection between direct or reverse operation for relay 2.
c3 = Default operation relay 1. In case of failure of probe 1:

oPn= relay 1 will remain open.
Clo= relay 1 will remain closed.

c4 = Default operation relay 2. In case of failure of probe 1 (for all modes excepting
ON OFF2) or in case of failure of probe 2 (for mode ON OFF2):

oPn= relay 2 will remain open.
Clo= relay 2 will remain closed.

P0 = Temperature scale selection.
P1 = Calibration of probe 1. Offset degrees to be added to probe 1.
P2 = Calibration of probe 2. Offset degrees to be added to probe 2.
P3 = Decimal point. If the displayed value of the probes is desired with decimals or
not.
P4 = Probe to be displayed. Probe always on the display. The other probe can be
seen pressing the keys SET+UP.

sd1= probe 1.
sd2= probe 2.

P5 = Number of probes. If P5=1, there is not ON OFF2 mode. If selected, it will
operate as ONOFF1.
H0 = Reprogramming. Parameter to reprogram the thermostat.
H1 = Keyboard protection.

To change the sets, enter into parameter and exit again. The protection setting
is momentarily released. It switches on again 1 minute after the last time a key
was pressed.
Yes= Keyboard Protected.
No=Keyboard non protected.

H2 = Operation of LED OUT1.
dir = On when relay 1 is ON.
inv = On when relay 1 is OFF.
H3 = Operation of LED OUT2.
dir = On when relay 2 is ON.
inv = On when relay 2 is OFF.
H4 = Serial communication address. Address for computer connection.
H5 = Parameter entry code. Factory set as 0.
H6 = Input probe type selectable between PTC or NTC.