Dwyer MTL7787 User Manual

Page 6

Advertising
background image

2

INM7700-6 Jan 2010

2.3

MTL7700 Series – accessories

MTL7700 Series barriers mount directly onto DIN-rail. A
comprehensive selection of mounting, tagging, power and earthing
accessories is available. Installation details are given in section 4.3.

Essential accessories

The following are usually considered essential for mounting and
earthing MTL7700 Series barriers:

DIN-rail (eg, THR2 or THR7000)
Insulating spacers (eg, ISP7000)
Earth terminal (eg, ETL7000)

The tagging systems for individual modules and columns of barriers
are described here. They are shown below under Tagging
accessories for columns of barriers.

Mounting accessories (figure 2)

THR2

Standard DIN-rail, 35 x 7.5mm, (in 1m lengths)

THR7000

Nickel-plated DIN-rail, 35 x 7.5mm, for use in
potentially corrosive atmospheres (in 1m lengths)

ISP7000

Insulating spacer: attaches to the base of a DIN-
rail to isolate the IS earth from a structural earth

Tagging accessories for individual barriers (figure 2)

TH7700

Tag holder for mounting on the top of an
individual barrier

Tagging accessories for columns of barriers (figure 2)

TAG57

Tagging strips for mounting over a column of
barriers, for marking barrier locations. Supplied
(with labels) in 1m lengths for cutting to size.

TGL7700

Spare labels for use with TAG57 tagging strips:
0.5m strips, supplied in sets of 10.

IMB57

Tagging strip supports. Two needed for each
tagging strip. It can also be used as centre
support by breaking off the top end tab.

Power accessories (figure 3)

BPL7700

Power link for feeding 24V dc to a maximum of
40 barriers in a single column from an MTL7798
power feed module or MTL7799 Dummy
module.

Earthing accessories (figure 3)

ETL7000

Earth terminal providing connections for
routeing the IS earth from the DIN-rail to an
appropriate plant earth. Two recommended for
each length of DIN-rail.

TAG57

TGL7700

ERB57O

IMB57

ETL7000

ISP7000

TH7700

Figure 2: MTL7700 Series mounting and tagging accessories

Table 1: MTL7700 Series Key barriers

Type

Application

Key barriers

MTL

Analogue Resistance temperature detectors

7755ac

input

Thermocouples, ac sensors

7756ac

(low-level)

7760ac

Analogue Controller outputs, one line earthed

7728+

output

Controller outputs, neither line earthed

7787+

dc power supply

26V

20-35V

Analogue Transmitters, 2-wire, 4–20mA

7787+

7706

input

(high-level)

Digital Switches

7787+

7707+

(on/off)

7741-44

input

Digital Solenoids,

alarms,

LEDs

7728+

7707+

(on/off)

output