Overview: Display Symbols and Buttons

Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001

3

Buttons

ON button: Press this button to switch ON the UPS or the External Bypass Static Switch.

OFF button: Press this button to switch OFF the UPS or the External Bypass Static Switch.

EMO (Emergency Module OFF) button: To be used in emergency situations only.
Pressing this button switches OFF all breakers, disabling AC/DC input and output in this section.
Be aware that this action may cut the supply to the load from the affected section.

Breakers

Note: Only operate a breaker when the associated breaker lamp is on.

Q1

UPS input breaker

Q5

Static bypass input breaker

Q2

UPS output breaker

Q6

Static bypass output breaker (optional)

Q3

Manual bypass breaker

Q7

Battery breaker 1

Q4

System output breaker (optional)

Q8

Battery breaker 2