American Dryer Corp. AD-230 User Manual

Page 19

Advertising
background image

15

2. MULTIPLE DRYER (Common) VENTING

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be

channeled into a "common main duct." The individual ducts should enter the bottom or side of the main

duct at an angle not more than 45º in the direction of the airflow. The main duct should be tapered, with the

diameter increasing before each individual 8-inch duct is added.

IMPORTANT: No more than eight (8) dryers should be connected to one main common duct.

NOTE: Refer to the illustration on page 16 for examples of multiple dryer (common) venting.

The main duct may be any shape so long as the minimum cross-sectional area is provided. The illustration

on page 16 shows the minimum cross-sectional area for multiple dryer venting. These figures must be

increased in proportion if the main duct run from the last dryer to where it exhausts to the outdoors is

unusually long (over 20 feet) or has numerous elbows (more than two [2]) in it.

IMPORTANT: For extended duct work runs, the cross section area of the duct work can only be

increased to an extent. Maximum proportional duct work runs cannot exceed 20

feet more than the original limitations of 20 feet with two (2) elbows. When the duct

work approaches the maximum limits as noted in this manual, a professional HVAC

firm should be consulted for proper venting information.

IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust

duct area should not exceed 0.3 inches W.C. (water column).

The duct work should be smooth inside with no projections from sheet metal screws or other obstructions

which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be

connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the

building. Also, inspection doors should be installed at strategic points in the exhaust duct work for periodic

inspection and cleaning.

NOTE: Where the exhaust passes through a wall, ceiling, or roof made of combustible materials, the

opening must be 2-inches larger (all the way around) than the duct. The duct must be

centered within this opening.

To protect the outside end of the horizontal duct work from the weather, a 90º elbow bent downward

should be installed where the exhaust exits the building. If the exhaust duct work travels vertically up

through the roof, it should be protected from the weather by using a 180º turn to point the opening

downward. In either case, allow at least twice the diameter of the duct between the duct opening and

nearest obstruction.

Advertising