For protection against excessive pressures and

temperatures, a temperature and pressure relief valve

must be installed in the opening marked “T & P RELIEF

VALVE” (see Figure 14). This valve must be design

certified by a nationally recognized testing laboratory

that maintains periodic inspection of the production of

listed equipment or materials as meeting the

requirements for Relief Valves and Automatic Shut-off

Devices for Hot Water Supply Systems, ANSI Z21.22.

The function of the temperature and pressure relief

valve is to discharge water in large quantities in the

event of excessive temperature or pressure developing

in the water heater. The valve's relief pressure must

not exceed the working pressure of the water heater

as stated on the data plate.

Explosion Hazard

If the temperature and pressure relief valve

is dripping or leaking, have a licensed

plumber correct the problem.
Do not plug valve.
Do not remove valve.
Failure to follow these instructions can

result in death, or explosion.

Important: Only a new temperature and pressure relief

valve should be used with your water heater. Do not

use an old or existing valve as it may be damaged or

not adequate for the working pressure of the new water

heater. Do not place any valve between the relief valve

and the tank.
The Temperature & Pressure Relief Valve:
·

Must not be in contact with any electrical part.

·

Must be connected to an adequate discharge line.

·

Must not be rated higher than the working pressure

shown on the data plate of the water heater.

The Discharge Line:
·

Must not be smaller than the pipe size of the relief

valve or have any reducing coupling installed in

the discharge line.

·

Must not be capped, blocked, plugged or contain

any valve between the relief valve and the end of

the discharge line.

·

Must terminate a maximum of 6 inches above a

floor drain or external to the building.

·

Must be capable of withstanding 250°F (121°C)

without distortion.

·

Must be installed to allow complete drainage of

both the valve and discharge line.

Temperature and Pressure

Relief Valve

Discharge Line

3/4 Inch Min.

DO NOT CAP OR PLUG

6 inch maximum

Drain pan

Drain

Figure 14: T & P Valve Installation

14