Setup and Programming

Note: See the MATE3
manual for details on
generator control.

Quick Start Guide

RADIAN Series

HUB 10.3

Communications

Manager

MATE3

System

Display and

Controller

Radian Inverter/Charger

GS Load Center

(GSLC)

FM80 Charge

Controllers

(x2)

WARNING: Fire/Explosion Hazard

Do not place combustible or flammable materials within 3.7 m (12 feet) of
the equipment. This unit employs mechanical relays and is not ignition-
protected. Fumes or spills from flammable materials could be ignited by sparks.

WARNING: Personal Injury

Use safe lifting techniques and standard safety equipment when working with
this equipment.

IMPORTANT:

Clearance and access requirements may vary by location. Maintaining a 90-cm
(36") clear space in front of the system for access is recommended.
Consult local electric code to confirm clearance and access requirements
for the specific location.

CAUTION: Equipment Damage

These procedures should be done by a qualified installer who is trained on programming inverter power systems.
Failure to set accurate parameters for the system could potentially cause equipment damage. Damage caused by
inaccurate programming is not covered by the limited warranty for the system.

IMPORTANT

Check the firmware revision of all OutBack devices before use. The Radian inverter and MATE3 system display may not
communicate or operate correctly unless their firmware is above a specified revision number.

For model GS7048E, the firmware must be revision 001.005.xxx or higher with a MATE3 revision of 002.010.xxx or higher.

For model GS3548E, the firmware must be revision 001.005.xxx or higher with a MATE3 revision of 002.017.xxx or higher.

The MATE3 Configuration
Wizard allows quick setup of
parameters that apply to all
systems. The Configuration
Wizard is reached from the
MATE3 Main Menu as shown
to the right.

The firmware revision of all
devices can be confirmed by
navigating from the MATE3
Main Menu as shown below.
Upgrades to the firmware
revision can be downloaded
from the OutBack website
www.outbackpower.com.

IMPORTANT:

Not intended for use with

life support equipment.

Contact Technical Support:
Telephone:

+1.360.618.4363

Email:

[email protected]

Website:

www.outbackpower.com

AC Source

Utility Grid or
AC Generator

Main Electrical Panel (or overcurrent
device for the AC source)

Electrical Distribution Subpanel
(Load Panel)

Photovoltaic (PV) Array

Battery Bank

Customer-Supplied Components

Optional OutBack Components

FLEXnet DC Monitor (FN-DC)

Remote Temperature Sensor (RTS)

Charge Controller

FLEXmax 80 depicted
(with FW-CCB2
mounting bracket)

PV Combiner Box

PV12 depicted

Communications

Manager

HUB10.3 depicted

EnergyCell depicted

Inverter/Charger

GS Load Center

System Display
and Controller

MATE3 depicted
(with FW-MB3
mounting bracket)

GS7048E
GS3548E

Radian System Products

Major Components

GSLC175-PV-230
GSLC175PV1-230
(both depicted)

S

Firmware Revision

Configuration Wizard

Off Grid

Grid Tied

Backup

This advances the display to the

Setup Complete screen.

C

C

C

S

S

S

C

This advances the display to the

Setup Complete screen if the
FLEXnet DC is not installed. If the
FLEXnet DC is installed, the display
advances to the

Shunt screens.

If FN-DC is installed...

If FN-DC is installed...

If FN-DC is installed...

Generator Installed Y
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1

Back Continue

New Configuration >>
Existing Configuration >>
Restore Configuration >>

System Type Grid Tied
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah

Back Continue

Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC

Back Continue

New Configuration Initialized

Back Continue

Shunt A
Connection Inverter

Back Continue

Shunt B
Connection Charge Controller

Back Continue

Shunt C
Connection Charge Controller

Back Continue

Period 1 Enable N

Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00

Back Continue

Period 2 Enable N
Weekday Use 0:00 Drop 0:00

Back Continue

Period 3 Enable N
Weekday Use 0:00 Drop 0:00

Back Continue

Shunt A
Connection Inverter

Back Continue

Shunt B
Connection Charge Controller

Back Continue

Shunt C
Connection Charge Controller

Back Continue

Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%

Back Continue

Shunt B
Connection Charge Controller

Back Continue

Shunt C
Connection Charge Controller

Back Continue

Period 3 Enable N
Weekday Use 0:00 Drop 0:00

Back Continue

Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%

Back Continue

Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00

Back Continue

Generator Installed N
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1

Back Continue

AC Output Voltage 230 VAC
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 30 A

Back Continue

Period 2 Enable N
Weekday Use 0:00 Drop 0:00

Back Continue

Generator Installed N
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1

Back Continue

Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC

Back Continue

AC Output Voltage 230 VAC
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 30 A

Back Continue

System Type Backup
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah

Back Continue

Shunt A
Connection Inverter

Back Continue

AC Output Voltage 230 VAC
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 30 A

Back Continue

Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC

Back Continue

System Type Off Grid
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah

Back

Continue

Settings >>
Configuration Wizard >>
Device Data Logs >>
Event Logs >>
Firmware Update >>

System >>
Inverter >>
Charge Controller >>
Battery Monitor >>
MATE3 >>

System

System Information >>
Save / Store Information

>>

Firmware Version >>
Date and Time >>
LCD Display >>

MATE3 002.017.018

1: GS7048E 001.005.002
2: GS7048E 001.005.002

Settings >>
Configuration Wizard >>
Device Data Logs >>
Event Logs >>
Firmware Update >>

Settings

Configuration Wizard

New Configuration

!