Insulation blankets – State EPX 80 DHPT User Manual

Page 11

Advertising
background image

11

Figure 9A

Junction Box

Ground

Wire

Conduit

(Field Connection)

Black Wire

Red Wire

Green

Ground

Wire

Red

Black

Approved Connectors

Figure 10

Wiring Diagram

Overload

Protection

To 240v

1 Phase

Power supply

Electrical

Service ground

L1

L2

Circuit

Breaker

Ground

Wire

Green

Connecting the Condensate Pump

Overflow Shut Off Switch

1. Turn off power to the electrical wiring for the water

heater at the circuit breaker/fuse box.

2. Locate the white 18 AWG wire loop behind the field

wiring junction box. See Figure 9B.

3. Cut the loop and strip insulation off of the two ends.
4. Measure the distance from the field wiring junction box

to the condensate pump, and cut two 18 AWG or larger

wires to correct length and strip the insulation at both

ends of each wire. See Figure 9B.

5. Connect these two wires to the two wires on the water

heater using wire nuts or other connectors.

6. Connect the free ends of the two wires to the shut off

switch on the condensate pump in accordance with the

manufacturers recommendations.

7. Turn on electrical power to the water heater.

8. Press the power button to turn the water heater on

and

select the desired operational mode. After about 8

minutes, the heat pump will turn on.

9. Test the operation of the shut off switch by unplugging

the condensate pump and filling the condensate

reservoir with water until the float switch opens the

circuit.

10. The heat pump should turn off and the error code

“CONDENSATE DRAIN ALARM “will appear on the

user interface screen.

11. Plug the condensate pump in and verify that the pump

operates and pumps the water out of the condensate

reservoir.

12. The error on the user interface should clear and the

heat pump should operate after 8 minutes.

Insulation Blankets

The use of an insulation blanket on this water heater is not

needed or recommended. The purpose of an insulation

blanket is to reduce the standby heat loss encountered with

storage tank heaters. Your water heater meets or exceeds

the National Appliance Energy Conservation Act standards

with respect to insulation and standby loss requirements,

making an insulation blanket unnecessary.

Figure 9B

Condensate Pump Wiring

Condensate Pump Wiring Loop

18 AWG - White

(Loop Located Behind Junction Box)

White Wires

From Water Heater

Wires to Condensate

Pump Overflow

Shut Off Switch

(18 AWG or Larger)