RELATIVE GAIN

.

to

.

This defines the gain of

OP2

relative to

OP1

. It is generally set to balance the

effects of cooling to that of heating(

r1d2

) or vice versa (

d1r2

). This is

illustrated in the Heat/Cool Relative Gain Figures below. After completion of

Auto-Tune, this parameter will be changed.

DEADBAND/OVERLAP



to



This defines the deadband area between the bands (positive value) or the

overlap area in which both heating and cooling are active (negative value). If a

heat/cool overlap is specified, the percent output power is the sum of the heat

power and the cool power. The function of Deadband/Overlap is illustrated in

the Control Mode Explanations.

.



b

OUTPUT 2 POWER LOWER LIMIT

.

to

.

%

This parameter may be used to limit controller power at the lower end due to

process disturbances or setpoint changes. Enter the safe output 2 low power

limit for the process. When the controller is in

USEr

or

OnOF

Control Mode, this

limit does not apply.

OUTPUT 2 POWER UPPER LIMIT

.

to

.

%

This parameter may be used to limit controller power at the upper end due to

process disturbances or setpoint changes. Enter the safe output high power limit

for the process. When the controller is in

USEr

or

OnOF

Control Mode, this limit

does not apply.

INPUT FAIL OP2 POWER LEVEL

This parameter sets the power level in the event of an input failure (open TC/

RTD or shorted RTD). Manual (

USEr

) Control overrides the input fail preset.

.

to

.

%

TEMPERATURE

COOL

HEAT

SETPOINT

100%

OP2

100%

OP1

2X PROPORTIONAL

BAND

%

OUTPUT

POWER

OP1

100%

SETPOINT

DEADBAND

NEGATIVE VALUE

COOL

RELATIVE GAIN = .5

.5

1

2

RELATIVE GAIN

OP2

100%

TEMPERATURE

HEAT

%

OUTPUT

POWER

TEMPERATURE

HEAT

SETPOINT

100%

OP2

100%

OP1

DEADBAND

POSITIVE VALUE

RELATIVE GAIN

2

1

.5

RELATIVE GAIN = .5

COOL

%

OUTPUT

POWER

HEAT/COOL RELATIVE GAIN FIGURES

Deadband/Overlap = 0

Deadband/Overlap < 0

Deadband/Overlap > 0

ON/OFF CONTROL HYSTERESIS

to



The On/Off Control Hysteresis (balanced around the setpoint) eliminates

output chatter. The control hysteresis value affects both OP1 and OP2 control.

The hysteresis band has no effect on PID Control. On/Off Control Hysteresis is

illustrated in the Control Mode explanations.

.



.



.

I

C

Shaded parameters are programming/model dependent.