Horner APG SmartRail HE599ADC170 User Manual
Smartrail, Prefer spring-clamps
MAN0931-02-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
1/3/2011
Page 1 of 1
1
Specifications
Specifications
ADC170
Number of Channels
4
Input Ranges
0-10V, 4-20mA, 0-20mA
Absolute Max. Inputs
+/-15V, +/-30mA
Resolution
12-Bit (2.5mV, 4uA, 5uA)
Input Impedance
1MΩ (voltage), 250Ω (current)
Accuracy
< +/-0.5%
Isolation
Photocoupler (Input/Power)
Conversion Time
1.5mS/ch
Backplane Power Consumed
50mA @ 5V
External Power Required
62mA @ 24V (+/-10%)
Terminal Type
Screw Type, Removable 11-posn
Optional Spring-clamp Plug
HE599TRM011
Storage Temp.
-25° to 70° Celsius
Operating Temp.
-0° to 55° Celsius
Relative Humidity
5 to 95% Non-condensing
Dimensions WxHxD
20mm x 90mm x 60mm
0.79” x 3.54” x 2.36”
Weight
67g (2.4 oz.)
CE & UL Compliance
CE, UL & C-UL
2
Wiring – I/O
3
Configuration DATA
The SmartRail ADC170 features a dip switch on the front of the unit for selecting voltage (0-10V) or
current (4-20mA or 0-20mA) on a per channel basis. In addition to the physical dip switch, Cscape
(9.1 or later) must be used for software configuration as well. The following parameters are
configurable in Cscape for the ADC170:
Cscape Configuration Data – Selectable per channel
Parameter
Selections
Enable
Channel Enable
Disable
4-20mA
0-20mA
Data Type
0-10V
0-4000
-2000 to +2000
0 to 1000 (for 4-20mA type)
Data Range
0 to 1000 (0-20mA or 0-10V type)
4
Installation / safety
a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields should be grounded at one end only, preferably at the end providing the best noise
shunting.
d. Use the following wire type or equivalent: Belden 8441.
For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
7
Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:
http://www.heapg.com
Email:
Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:
http://www.horner-apg.com
Email:
ADC170 LED Status Indication
LED
Meaning
ON = Normal Operation
FLASH = I/O Error
RUN
OFF = No Power or I/O Error
SmartRail
0-10V, 4-20mA Analog Input Module
HE599ADC170
12-Bit Resolution
No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.
Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.
Warning: Consult
user documentation.
Warning: Electrical
Shock Hazard.
+
-
24VDC
N.C.
-
CH4
+
-
CH3
+
-
CH2
+
-
CH1
+
CH1
CH2
CH3
CH4
V
I
24VDC @ 62mA
External Power
SHIELD GROUNDED
AT ONE END ONLY
0-10V
0-10V
+
+
+
-
-
-
LOOP
POWER
4-20ma
+
-
+
-
LOOP
POWER
4-20ma
+
-
+
-
Prefer Spring-clamps?
Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).
Representative 10-position plug shown.