American Sensor SA379 User Manual

Ionization, À ionisation, Smoke alarm

Advertising
background image

SMOKE ALARM MANUAL

Ionization Type Model - 120 VAC Hardwire

with Battery Back-Up & Alarm-Pause

¨

Feature

€ Model SA379 - Multi-Location

- 120 Volt AC Hardwire Smoke Alarm with Battery Back-Up

and Alarm-Pause

®

feature. This smoke alarm is also

interconnectable with up to 11 other units.

Important information about your smoke alarm

Install alarms outside of every bedroom area and on every floor

of your home. Please refer to Section 3 •

Where to Locate Smoke

AlarmsŽ for details.

Install the alarm as close as possible to the center of the ceiling.
Your Smoke Alarm is packaged with the back-up battery

reversed. Connect it before mounting the unit. Ensure proper

polarity of the battery. Alarm will •

beepŽ if battery is reversed

and the unit is receiving AC power.

Replace the back-up battery if the smoke alarm beeps

approximately once every 45 seconds (low battery warning).

Test the alarm weekly by pressing and holding the test button

for up to 20 seconds until the alarm sounds.

The model described in this manual is designed for single

family residences, including homes and apartments.

SA379 Smoke Alarm Safety Features

€ Battery Back-Up - 120VAC operation with battery back-up

(included) to power your smoke alarm in the event of a power

interruption.

€ Alarm-Pause

®

Silencer - Silence your alarm for approximately

10 minutes, by momentarily pressing the Alarm-Pause

®

Silencer

button. Ideal for use when non-emergency smoke causes

nuisance alarms. Automatically resets after 10 minutes. During

Alarm-Pause

®

the unit will •

beepŽ every 45 seconds to remind

the household that the alarm has been silenced. In the event of

a heavy build-up of smoke during the pause period, the alarm

will resume sounding. For interconnected units, only the alarm

which had the Alarm-Pause

®

Silencer button activated will be in

Alarm-Pause

®

.

€ Dual-Ionization Chambers - Advanced design responds to

visible or invisible particles of combustion (smoke) to sense fires

in their earliest stages. Compensates for changes in humidity and

temperature to virtually eliminate •

nuisanceŽ alarms caused by

normal atmospheric changes in the home.

€ Operating Lights (LED• s) - A continuous green light located

behind the slotted case indicates the smoke alarm is receiving

AC power. A red light that flashes approximately every 45

seconds confirms that the battery is operational.

€ Low Battery W arning - If powered only by battery the unit

beepsŽ approximately every 45 seconds for up to 30 days when

the battery needs replacing. If the unit is receiving continuous

AC power, the low battery beep will continue indefinitely.

€ Battery Removal Indication - Battery compartment drawer is

designed to resist closing when the battery is removed. A visual

reminder to replace the battery. Low battery warning beep is

disabled with the drawer open.

€ Interconnection - Interconnection facilities for up to 11 other

units, using only three wires, including AC power. When one

alarm sounds, all properly interconnected smoke alarms follow.

NOTE: Interconnect only to the models specified in Section 6.

€ Alarm Source Indicator - Only the red operating light in the

unit originating the alarm will flash rapidly in the event of an

alarm. With interconnected units, an easy check to determine

the originator.

€ Locking Keys - Two auxiliary locking keys provided. Use key #

1 to lock mounting plate to smoke alarm. Use key # 2 to lock

mounting plate and battery drawer to the smoke alarm to

prevent opening of the battery drawer. Reduced risk of

unauthorized removal.

€ Sensitivity T est Button - Tests sensitivity, as well as circuitry,

battery and horn. With interconnected units, activating test

button on one unit will cause all units to sound. An important

and convenient check of system integrity.

€ Quick Disconnect Power Connection - For easy installation.

Connect the wires separately from the unit and then plug into

back of the unit.

€ Detachable Base Plate - For easily securing the alarm to the

junction box.

CONTENTS OF THIS MANUAL

1. CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS
2. SAFETY TIPS
3. WHERE TO LOCATE SMOKE ALARMS
4. NFPA RECOMMENDATIONS
5. LOCATIONS TO AVOID
6. INSTALLATION AND TESTING
7. BATTERY REPLACEMENT
8. MAINTENANCE AND TROUBLESHOOTING
9. LIMITED WARRANTY
10. OTHER AMERICAN SENSORS PRODUCTS

1. CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS

American Sensors smoke alarms are designed to provide early

warning of fire and smoke at reasonable cost. Early warning can

mean the difference between a safe escape and no escape at all.

While smoke alarms can provide invaluable protection for you and

your family, they do have limitations.
€ Smoke alarms cannot work without power . Battery operated

alarms will not work without proper batteries, with dead

batteries or if batteries are not properly installed. AC powered

alarms will not work if their AC power supply is cut off by an

electrical fire, an open fuse, a circuit breaker or any other reason.

If you are concerned about the reliability of either batteries or

your AC power supply for any of the above reasons, you should

install in your home both AC and battery powered smoke alarms

for added security. This American Sensors Smoke Alarm model

SA379 is AC powered with battery back-up and offers superior

protection from the dangers of smoke and fire.

€ Smoke alarms are incapable of sounding the alarm until

smoke reaches the sensing chamber. Anything preventing

smoke from reaching the alarm may delay or prevent an alarm.

A smoke alarm cannot detect fire in the walls, chimney or roof

unless and until a significant amount of smoke reaches the

alarm. A closed door may prevent smoke from reaching an alarm

on the other side of the door. A smoke alarm may not sense a

fire on another floor of a home. For example, a basement smoke

alarm may not detect a fire which started on the first or second

floor.

€ Smoke alarms may not be heard. The loudness of the horn in

your alarm meets current standards. However, the sound may be

blocked by distance, closed doors, or ambient noise such as traffic

or a stereo. Smoke alarms may not be heard by persons who are

hard of hearing. For these reasons, a smoke alarm should be

installed in every room or at least on every level of your home.

American Sensors recommends that hardwire AC Powered smoke

alarms be interconnected, so that one alarm will trigger all other

Smoke alarms to sound their alarms.

€ Smoke alarms are not fool-proof. Smoke alarms may not always

sense every kind of fire. They cannot be expected to sense fires

caused by carelessness or by safety hazards. They may not give

early warning of fast growing fires caused by smoking in bed,

violent explosions, escaping gas, improper storage of flammable

materials, overloaded electrical circuits, natural causes such as

lightning, children playing with matches, or arson.

€ Smoke alarms are not substitutes for property , disability, life or

other insurance of any kind. Home owners and renters should

continue to insure their lives and property. Consult your

insurance agent.

€ Smoke alarms have limited lives. One or more of the many

components could fail at any time. Therefore, test your smoke

alarm weekly. Clean and take care of it as described in this

manual. Repair or replace the smoke alarm when it fails to test

properly. Your smoke alarm should be replaced if it is ten years

old.

A photoelectronic smoke alarm senses smoke using an electronic

photo receptor to sense the scattering of light by smoke particles.

2. SAFETY TIPS

Properly installed and maintained smoke alarms are an essential part

of a good home fire safety program. Your fire safety program

should also include a review of fire hazards and the elimination of

dangerous conditions whenever possible. Consider the following

tips:
Use smoking materials properly. Never smoke in bed.
Keep matches and cigarette lighters away from children.
Store flammable materials in proper containers. Never use them

near an open flame or sparks.

Keep electrical appliances in good condition. Do not overload

electrical circuits.

Keep stoves, fireplaces, chimneys, and barbecue grills grease free.

Make sure they are properly installed and away from any

combustible materials.

Keep portable heaters and open flames such as candles away from

combustible material.

Do not allow rubbish to accumulate.
Keep a supply of extra batteries on hand for your battery powered

smoke alarms.

Do not stand too close to the alarm when the unit is in alarm as

the loud horn could damage your hearing.

Never disconnect the battery or the AC power

on any type of smoke alarm to silence a nuisance alarm. Clear the

area of smoke by opening doors or windows or fanning the smoke

away. Use the Alarm-Pause

®

button on model SA379 to silence

nuisance alarms.
Most important, when fire strikes, a prepared and practiced

escape plan can make the difference between life and death.

Develop an escape plan and practice it with the entire family,

including small children.
Ensure all family members are familiarized with the alarm signal.
Prepare an escape plan. Draw a Floor Plan of Your Home and

determine two exits from each room. There should be a way to get

out of each bedroom without opening the door.

Have Fire Drills Often. Practice your Escape and BE PREPARED.
Decide on a meeting place at a safe distance from your home.

IN CASE OF FIRE

Don•t waste time collecting possessions after a fire starts.
Arouse all occupants and leave the building. Your most valuable

possession is your life.

Doors can mean escape or death. Never open doors without first

checking for heat. Test them with your hands, if they feel warm,

fire may be walled up behind them - leave closed and find another

escape route.

Call the fire department from OUTSIDE the building.
If trapped inside, stay close to the floor, cover mouth with cloth,

conserve breath as you crawl to safety.

Keep all doors and windows closed except for escape purposes.
NEVER re-enter a burning building.
Keep your family in a pre-arranged meeting place after your

escape.

Your local fire department may be able to offer you additional ideas

for safety and escape plans in the home.

3a. WHERE TO LOCATE SMOKE ALARMS

As a minimum, smoke alarms should be located between sleeping

areas and potential sources of fire such as a kitchen, heated garage

or basement. In single storey homes with one sleeping area, an

alarm should be installed in the hallway outside the bedrooms (see

Figure 1). In single storey homes with two separate sleeping areas, a

minimum of two alarms are required, one outside each sleeping area

(see Figure 2). In multi-level or split-level homes, as a minimum, an

There are two different types of smoke alarm technology

currently in general use: Ionization and photoelectronic.

While both types of technology are suitable for general

residential use, an ionization alarm will normally respond

faster to fast flaming fires, while a photoelectronic alarm

may be more sensitive to detecting slow smouldering fires.

Because home fires develop in different ways and are often

unpredictable in their growth, it is impossible to predict

which type of alarm will provide the earliest warning. For

best home protection install at least one photoelectronic and

one ionization smoke alarm on each level of your home.

Model SA379 is an ionization type smoke alarm.

Ionization Technology vs.

Photoelectronic Technology

Smoke Alarms

alarm should be installed outside each sleeping area, in the

basement and at every level of the home (see Figure 3).
In every room of your home (except the bathroom): Research

indicates that substantial increases in warning time can be

obtained with each properly installed, additional alarm.

In bedrooms: In anticipation of fires originating within these

rooms, caused by faulty wiring, lamps, appliances, smoking or

other hazards.

In hallways: At a distance no greater than 4 meters (13 feet) from

the farthest wall and no greater than 8 meters (26 feet) from the

next alarm.

In the center of a room or hallway: As it is impossible to predict

the source of a fire. If it is necessary to place the alarm on a wall,

always locate the top of the smoke alarm 10-15 cm (4-6 inches)

from the ceiling.

As needed: To compensate for closed doors and other obstacles

that may interfere with the path of smoke to an alarm. They may

also prevent occupants on one side of a closed door from hearing

an alarm on the other side of the door.

Model SA379 - Multi-location Hardwire with Battery Back-Up

Model can be located in any area of the home. Its

Alarm-Pause

®

feature makes it ideal in the kitchen area

to silence nuisance alarms. Do not install it directly over

a stove, toaster or dishwasher.
READ •

CAP ABILITIES AND LIMITATIONS OF SMOKE

ALARMSŽ in Section 1 of this manual.
Your local fire department or insurance company may be able to

give you further advice on the best smoke alarm locations in your

home. Call them and ask.

These diagrams show smoke alarm locations as recommended as

above in 3a.

3b. WHERE TO LOCATE SMOKE ALARMS IN MOBILE HOMES

AND RECREATIONAL VEHICLES (RVÕs)

Note: Power supply must be 120 Volts AC for model SA379.

In mobile homes and RV•s built after 1978 locate the smoke alarm

as described above.
Older mobile homes and RV•s may have little or no insulation

compared to the ones built post 1978. These uninsulated exteriors

can disrupt airflow around the smoke alarm in hotter or colder

weather. Locate the alarm only on interior walls 10 to 15 cm (4"

to 6") from ceiling 1. if you own an older mobile home or RV, or 2.

if you notice the exterior walls and/or ceiling are noticeably cold or

warm or 3. if you are uncertain about the quality of insulation.
Regardless of the age of the mobile home or RV, locate alarms

throughout to ensure maximum protection. Follow the location

instructions in this manual.

4. NFPA RECOMMENDATIONS

For your information, the National Fire Protection Association•s

Standard 72, Section 2-2.1.1.1, reads as follows:
2-2.1.1.1 Smoke alarms shall be installed outside of each separate

sleeping area in the immediate vicinity of the bedrooms

and on each additional storey of the family living unit,

including basements and excluding crawl spaces and

unfinished attics. In new construction a smoke alarm also

shall be installed in each sleeping room.

5. LOCATIONS TO AVOID

Avoid locations where smoke may not reach the alarm in time to

provide early warning, or where the alarm may not be effective.
DO NOT PLACE SMOKE ALARMS:
€ In turbulent air
from fans, doors, windows, etc. The rapid air

movement may prevent combustion particles from entering the

alarm.

€ In dead air spaces such as at the peak of an •

AŽ frame ceiling.

Dead airŽ at the top may prevent smoke from reaching the alarm

in time to provide early warning. In rooms with simple sloped,

peaked or gabled ceilings, install smoke alarms on the ceiling 90

cm (3 feet) from the highest point of the ceiling.

Note: For complex ceiling structures, consult a safety expert for

the number of alarms required and the best locations.

€ In very hot or cold areas where the temperature exceeds 38

0

C

(100

0

F) or falls below 5

0

C (40

0

F).

Less than 15 cm (6 inches) from the wall when mounted on the

ceiling.

Nuisance alarms could result when smoke alarms are located where

interference may occur with the sensing chamber. To avoid

nuisance alarms, DO NOT place smoke alarms:
€ In high humidity areas
such as bathrooms and attics. Place

smoke alarms at least 3 meters (10 feet) away from bathrooms.

€ In insect-infested areas.
€ In poorly ventilated kitchens or garages.
€ In very dusty and dirty areas.
€ Near fluorescent lights.
Place smoke alarms at least 1.5 meters (5

feet) from fluorescent lights.

This smoke alarm is suitable for residential use.

It is not to be connected to a commercial or industrial fire alarm

panel.

6. INSTALLATION AND TESTING

Locking Keys - Optional

This model has optional locking keys to better secure either the

alarm and/or the alarm and back-up battery to inhibit unauthorized

removal. See point 16 in this section for more details on this

feature.

A. Installation

Mount to any standard or rectangular junction box with a minimum

depth of 25mm (1 inch). 120V AC, 55mA operation.
WARNING: Wiring should only be installed by a licensed

electrician in accordance with the Canadian Electrical Code, Part I,

and local codes.
WARNING: All AC-powered interconnected smoke alarms shall be

installed on the same circuit (i.e., the same circuit breaker/fuse). The

electrical circuit must be a 24-hour voltage circuit that cannot be

turned off by a switch or Ground Fault Interrupter. It is important that

the power to each alarm is taken from the same point within the circuit

and the polarities are maintained on each alarm. Following these

instructions will prevent false alarming due to electrical system

imbalances and damage to the units due to incorrect polarities. It is

highly recommended that smoke alarms be wired on a separate

circuit (one with no other lights or appliances) to ensure maximum

reliability of AC power supply.

For installation of Smoke Alarms in Dwelling Units, it is important

to follow the Canadian Electrical Code (1994) Part 1, Section 32-

110.

1. Electricity must be turned off at service entrance before

beginning installation to prevent electrical shock or equipment

damage.

2. Location must comply with applicable building codes.

3. Install a junction box where you plan to install the alarm. Use

standard 14 gauge wire.

4. Grasp the tab on the battery drawer and slide it straight out.

5. Reposition the battery in its compartment as shown on the

markings in the drawer.

6. Push the drawer straight in until it is flush with the housing.

7. Test as recommended in •

OperationŽ section.

8. Connect black and white wires, color to color, from power

connector to AC power leads.

9. For multiple station, use the orange wire for interconnection. If

unit is not to be interconnected, cap unused wire.

10. Loosen or remove screws from junction box.

11. Attach flat side of mounting plate and tighten screws to fit

snugly against junction box and ceiling or wall.

12. Bring power connector through center opening.

13. Slip the paper gasket supplied with the alarm over the power

connection and then onto the mounting plate so that the four

plastic tabs on the mounting plate will hold the gasket in place.

The gasket will prevent downward air currents from entering the

smoke alarm through holes in the back of the alarm. Unless

blocked off, downward air currents prevent smoke from entering

the alarm.

WARNING: IT IS IMPERATIVE THAT YOU INSERT THE

GASKET WHEN INSTALLING YOUR SMOKE ALARM.

14. Plug wire connector into the back of the alarm.

15. Align the plug area on the smoke alarm with the cut out in the

gasket and place the smoke alarm in the mounting plate, turn

clockwise to fasten it to the mounting plate.

16. If auxiliary lock is desired insert either key # 1 or # 2 into the

slot marked •

Key SlotŽ in the base of the alarm just below the

battery drawer. Locking key should •

clickŽ into position and be

flush with the alarm housing (keys are enclosed with the alarm

in plastic wrapper).

CAUTION: Do not attempt to remove alarm or open battery

drawer without first removing locking key. If key is not first

removed, damage may result (see below).

17. Test alarm operation after installation in accordance with

Operation: How to T estŽ instructions.

NOTE: Maximum interconnect wiring length is 50 meters (150

feet).

IMPORTANT: The SA379 is not interconnectable with any other

model produced by another manufacturer. The SA379 may be

interconnected only with the following ULC listed smoke alarm

models:

American Sensors

SA379

American Sensors

SA360

ASI Electronics (American Sensors)

ESA5010

ASI Electronics (American Sensors)

ESA5011

Dicon Safety Products Inc.

670L

Dicon Safety Products Inc.

670LR

Dicon Safety Products Inc.

370LBX

For a more complete discussion of installation and location

requirements refer also to: CAN/ULC-S553-M86 •

Standard for the

Installation of Smoke AlarmsŽ (available from Underwriters

Laboratories of Canada, 7 Crouse Road, Scarborough, Ontario M1R

3A9)

To Remove Locking Key

To remove the locking key, insert a small screwdriver into the small

hole at the top of the battery drawer. Apply pressure at the tip of

the screwdriver, pushing up on the locking key. The locking key will

pop out.

To Activate the Alarm-Pause

®

Feature

Simply press the Alarm-Pause

®

button on the cover of the smoke

alarm for a minimum of 5 seconds then release to activate the

Alarm-Pause

®

feature. In this mode, the unit should not respond to

smoke (by sounding an alarm) for a period of approximately 10

minutes, unless the level of smoke concentration becomes very

heavy (approaching 4 per cent per foot obstruction). During the

Alarm-Pause

®

period, the smoke alarm should •

beepŽ approximately

once every 45 seconds to alert the household that the smoke alarm

has been silenced.

Variations in Length of Alarm-Pause

®

Period

The Alarm-Pause

®

period will vary in length depending upon the

amount of smoke present. When there is no smoke, the Alarm-

Pause

®

will be activated for the longest period of time

(approximately six to ten minutes) after releasing the Alarm-Pause

®

button.

If the level of smoke density increases, the length of the Alarm-

Pause

®

period will shorten. As the level of smoke density approaches

4 per cent per foot obstruction (a very heavy concentration of

smoke), the smoke alarm will override the Alarm-Pause

®

mode and

sound an alarm. NOTE: If powered only by battery, the level of

battery voltage will also affect the length of the Alarm-Pause

®

period. If the battery voltage is low, the Alarm-Pause

®

will be

activated for approximately 10 minutes. If the battery voltage is

high, the Alarm-Pause

®

will be activated for a shorter period of time

(approximately 4 minutes).

To secure smoke alarm
to mounting plate and
also secure back-up
battery.

To secure
smoke alarm to
mounting plate.

IONIZATION

SMOKE ALARM

with Battery Back-Up

AVERTISSEUR DE FUMÉE

À IONISATION

avec pile de secours

READ C AREFU LLY AND SAVE.

T his manual contains important information.

A copy of this manual must be left with the end user.

LIRE AT T ENT IVEMENT ET C ONSERVER C E MANU EL.

Le présent manuel renferme des renseignements importants.
U n exemplaire de ce manuel doit être remis
à l utilisateur final. (Français au verso)

2502-2519

U

N

D

ER

W

RIT

ERS

' LABORATORIES

OF

CA

NA

D

A

LISTED BY

LA

BO

RA

TO

IRE

S DE

S ASSUREUR

S D

U

CA

NA

D

A

HO

MOL

OGUƒ PA

R

M OD E L /M OD È L E

SA 379

B. Operation: How to Test

Before Installation:

1. Connect battery. Ensure that the battery is correctly installed.

Positive terminal to positive contact and negative terminal to

negative contact, as indicated in the battery drawer. Reversing

the battery in the compartment should not cause any damage to

the smoke alarm. If the drawer is pushed all the way in, a low

battery beep will sound when the AC power is applied after

installation if the battery is improperly installed.
Storage in low humidity, and certain transportation conditions,

may cause electrostatic charges to build up in the alarm system

housing. Although harmless, these charges may increase the

length of time during which the horn sounds upon battery

insertion or test button operation. The condition may be cleared

by gently wiping the outside of the plastic cover with a clean,

damp cloth.

2. Check that the red operating light flashes approximately every

45 seconds.

3. Depress and hold the test button until the alarm sounds. NOTE:

It may be necessary to depress the test button for up to 20

seconds for an alarm to sound. An alarm is indicated by a loud

continuous pulsating sound. An alarm may continue to sound

for up to 10 seconds after the button is released.

After Installation
1. Check to see that the green operating light is on. The operating

light is visible behind the slotted case and confirms that the

smoke alarm is receiving AC power.

2. At least once a week, press the test button until the alarm

sounds, then release.

NOTE: Multiple Station Only:
3. Test each alarm separately in the system.
4. Determine that the initiating alarm triggers other alarms in the

system.

7. BATTERY REPLACEMENT

The Eveready 216, 522, 1222, Duracell MN1604 and the Gold Peak

1604P are the only acceptable back-up batteries for use in this

smoke alarm. The back-up battery will power the smoke alarm for at

least one year under normal use. When the back-up battery reaches

the end of its normal life, a low battery warning (intermittent

beeping) for up to 30 days, will indicate the need for back-up

battery replacement.
NOTE: If the battery drawer is open, the low battery warning beep

is disabled. The battery drawer is designed to resist closing when the

back-up battery is removed, thereby ensuring visual warning.

Use of a non-recommended battery may be

detrimental to the proper functioning of the alarm.

8. MAINTENANCE & TROUBLESHOOTING

VACUUM EVERY SIX MONTHS

Your smoke alarm should be cleaned every six months to help keep

it working efficiently. REMOVE POWER TO ALARM. Gently

vacuum through the vents of the alarm with a soft brush

attachment. Keep vacuum nozzle from touching the unit.

RE-ESTABLISH POWER TO ALARM.

Problems are indicated by these events:

1. The alarm does not sound upon pressing the test button.

2. The green operating light does not remain steadily on when the

unit is AC powered.

3. The red operating light remains steadily on or off (i.e. does not

flash once every 45 seconds, when the unit is not in alarm).

Try the following:

1. Inspect breaker or use in power circuit to alarm.

2. Check that the unit contains recommended battery type.

3. Check the battery is properly connected (Observe polarity).

4. Gently vacuum as recommended above.

5. Replace battery.

6. Call a trained, experienced serviceman to inspect house wiring

and connection to alarms.

If these procedures do not correct the problem, do NOT attempt

repairs. If the smoke alarm is within warranty period and terms,

indicate the nature of the problem and return the unit with proof of

purchase to the point of purchase, distributor or manufacturer. See

below for instructions. Units beyond warranty cannot be

economically repaired.

FALSE ALARMS:

Model SA379: Press the Alarm-Pause

®

button to silence nuisance

alarms.

Abnormal air conditions may cause the highly sensitive smoke

alarm to give a •

falseŽ alarm. If no fire is apparent, ventilate the

room and/or blow fresh air into the unit until the alarm stops. Once

cleared, the smoke alarm will automatically reset.

DO NOT DISCONNECT THE AC POWER OR THE BACK-UP

BATTERY

Dust can lead to excess sensitivity. Vacuum as recommended above.

9. LIMITED WARRANTY

Your American Sensors SA379 Smoke Alarm, excluding the battery

is warranted for ten years from the date of purchase against defect in

material and workmanship. Units returned to Dicon Gobal Inc.

with proof of purchase date during this period as a

result of such defects will be repaired, or replaced at

Dicon Global Inc. option, without charge. This warranty

only covers defects in material or workmanship in normal

residential use and does not cover the battery, nor does this

warranty cover damage resulting from negligent handling, misuse, or

lack of reasonable care. This warranty is in lieu of any other

warranty either expressed or implied.

DICON GLOBAL INC. SHALL HAVE NO

LIABILITY FOR ANY PERSONAL INJURY OR PROPERTY

DAMAGE, OR ANY SPECIAL INCIDENTAL, CONTINGENT

OR CONSEQUENTIAL DAMAGE OF ANY KIND RESULTING

FROM A FIRE. THE EXCLUSIVE REMEDY FOR BREACH OF

THE LIMITED WARRANTY CONTAINED HEREIN IS THE

REPAIR OR REPLACEMENT OF THE DEFECTIVE PRODUCT

AT DICON GLOBAL INC.S OPTION. IN NO

CASE SHALL DICON GLOBAL INC.S

LIABILITY UNDER ANY OTHER REMEDY PRESCRIBED BY

LAW EXCEED THE PURCHASE PRICE. YOUR SMOKE

ALARM IS NOT A SUBSTITUTE FOR PROPERTY,

DISABILITY, LIFE OR OTHER INSURANCE OF ANY KIND.

APPROPRIATE COVERAGE IS YOUR RESPONSIBILITY.

CONSULT YOUR INSURANCE AGENT.

This warranty gives you specific legal rights and you may also have

other rights which vary from province to province.

Return to point of purchase for servicing. Or, for repair or

replacement within the warranty period, return this product (or

send it postage prepaid) along with proof of purchase date to

Dicon Global Inc. Please enclose a note stating the

nature of the difficulty. Prior to sending, please call our toll free 1-

800 line (1-800-387-4219) to establish a Returned Goods

Authorization (•

RGAŽ) number and the latest instructions to

serve you promptly. Please mark this number on the exterior of

your package.

Dicon Global Inc.

20 Steelcase Road, Unit 3

M a r k h a m , Ontario, Canada

L3R 1B2

Healthy Home Hotline: 1-800-387-4219

10. AMERICAN SENSORS PRODUCTS

American Sensors offers a complete line of smoke alarms. Select

from this group of quality products to ensure your home is fully

protected in case of fire.

American Sensors also offers a complete line of Carbon Monoxide

Alarms including:

CO800

EL

- Plug-In Carbon Monoxide Alarm with night light

CO800 -

Plug-In Carbon Monoxide Alarm

CO810 -

120 Volt AC Hardwire Carbon Monoxide Alarm

CO900 -

Plug-In Carbon Monoxide Alarm with Battery Back-

Up

CO910 -

Plug-In Carbon Monoxide Alarm with Digital LED

Display

CO920 -

Plug-In Carbon Monoxide Alarm with Digital LED

and Back-Up Power Source

CO1100

G

- Battery Powered Carbon Monoxide Alarm for Table

Top, Travel or Wall Mount

AMERICAN SENSORS

CARBON MONOXIDE ALARMS

AMERICAN SENSORS SMOKE ALARMS

Model

SA308

SA318

SA358

SA388

SA900

SA360

SA379

SA700

Description

General Purpose Model

Kitchen Area Model with

Alarm-Pause

®

Feature

Hall and Stairways Model

with Emergency Light

Photoelectronic

Multi-Location Model

Long Life Multi-

Location with

Alarm-Pause

®

Model

Hardwire Multi-

Location Model

Hardwire with Battery

Back-Up and

Alarm-Pause

®

Model

2 in 1 Smoke Alarm

Power Source

9V Battery

9V Battery

2-9V Batteries

9V Battery

Long Life Lithium

battery with 10

year warranty

120 Volt AC

120 Volt AC with

9 Volt

Back-Up Battery

9V Battery

Smoke Alarm

Technology

Ionization

Ionization

Ionization

Photoelectronic

Ionization

Ionization

Ionization

Ionization/

Photoelectronic

Advertising