The Contractor shall furnish, where indicated on the plans, a Water Leak Detection System. The standard features shall include

but not be limited to the following:

1. The system shall utilize linear water leak detection cable.

2. The system shall utilize limited power, low voltage A.C. for the detection circuits to protect the leak detection cable from

damage by electrolysis.

3. The system shall supervise the wiring and the water sensing conductors embedded in the leak detection cable. Any break

in the wiring shall cause a System Trouble indication at the leak detection control panel.

4. The system shall also include both Alarm and Trouble indications for each input zone as was as a common audible alarm

and auxiliary form-C contacts for connection to external monitoring systems.

5. System inputs shall have adjustable sensitivity to allow for proper operation over a broad range of ambient field conditions.

6. The control panel shall operate from 115 V.A.C. and shall include automatic battery backup using a 12v gel - cell battery.

The panel assembly is housed in a steel enclosure with hinged door and cam lock to prevent unauthorized access.

7. The system shall be Model WD-1 / -4 -8 -16 (specify) as manufactured by AquaALERT, a division of LED Incorporated.

WD

SERIES

DETECTION SYSTEM

ZONE LEAK

COM COM

- 12v

+5v +5v +12v

Sonalert

Z2

Z3

Z4

Programming Connector

Output to Status Board

Trouble

Future Serial Port

XPor t

RJ-45 output jack

Form "C" Contacts

System Inputs

connections

NC

NO

NO

COM

COM

NC

Alarm

120 VAC Input

12v Battery

Power Supply

+

-

-

+

12 vdc Battery Output

12 vdc Power Output

H N

CAUTION

System Enclosure

Z1

Power Supply

120 vac input

12 vdc output

H

N

12v Battery

+ -

Battery Input

Detection Zone

Terminate w/15kohm 1/4watt

System Contacts

Sensitivity Adj.

Enclosure

CAUTION

120 VAC

WD-4

WD-1

NOTES:

Nominal power is 115v AC - 60hz - 500ma. Route power away from all class-2 wiring. Power supply is a universal type

with an input voltage range of 85 -264v AC and 47 to 63hz. Output is approximately 13.5v DC, 2 amps max with

self-restoring overload protection.

Standby power is provided by a 12v 1.5 amp/hr gelled electrolyte battery. System Alarm and Trouble contacts are rated

for 1amp resistive load, max. (class 2) Relays shown de-energized. Each leak detection zone must be terminated with

a 15K ohm resistor.

10"

10"

WD-1

WD-4

Front View

Side View

Door

Backbox

4"

1"

Front View

WD-1

WD-4

WD-8

18"

9"

Architect/Engineer Specification