Sunlight Supply Grozone Control SCC1 Temperature, Humidity and CO2 Controller Simple One Series User Manual

Page 11

Advertising
background image

11 of 12

Grozone SCC1 Advanced User Guide – March 2012

www.grozonecontrol.com

CHANGING THE OUTPUT CONTROL PARAMETER

Turn the SELECT knob (Day Temperature) to position 2. The two top PARAMETER indicators will lit.

CLICK the Pushbutton to select the VALUE Indicator (A to F) you need to turn ON (Lit) or OFF.

Rotate the SET/RESET knob (Humidity Temperature) to turn ON/OFF the selected indicator (selected

indicator is flashing; flashing will stop once value has been set or reset).

To EXIT and SAVE, make sure to move through all 6 indicators. Successful saving will blink the VALUE

indicators 4 times.













Indicator Name

Effect on Settings

(Factory Setting in Bold)

Indicator Name

Effect on Settings

(Indicator OFF is Factory Setting)

COOL
Control Range

Indicator is Off : +/- 2°F around setpoint

Indicator is Lit : +/- 4°F around setpoint

HEAT
Control Range

Indicator is Off :
Fixed range, -8°F to -2°F below setpoint

Indicator is Lit:
Auto range, -8°F to -2°F OR -12°F to -6°F below
setpoint to avoid competing equipment to operate
simultaneously

HUMIDITY
Control Range

Indicator is Off : +/- 2% around setpoint

Indicator is Lit : +/- 4% around setpoint

CO2
Control Range

Indicator is Off : +0 / - 200 ppm below setpoint

Indicator is Lit : +0 / - 400 ppm below setpoint

Low Temp
Limit

Indicator is Off : -6°F below setpoint

Indicator is Lit : -10°F below setpoint

High Temp
Limit

Indicator is Off : +10°F above setpoint

Indicator is Lit : 90°F regardless of setpoint















Ex. COOL, HUMIDITY and CO2 Control Ranges have been set to alternate settings.