WIKA DPT-10 User Manual
Page 83
l
primary_value
-
Process Value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'C
hannel' = 1. Unit derives from 'Primary_value_unit'
l
primary_value_unit
-
Unit code of 'Primary_value'
-
%
l
secondary_value_1
-
Process pressure. Selected as input to AIFB by setting 'Channel' = 2. Unit derives from
'S
econdary_value_1_unit'
l
secondary_value_1_unit
-
Unit code of 'Secondary_value_1'
-
bar, PSI, …, m, ft, …; in case of length type engineering unit and access to parameters the
corresponding values will be converted by density factor
l
secondary_value_2
-
Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'
l
secondary_value_2_unit
-
Selected unit code for "secondary_value_2"
l
sensor_value
-
Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'S
ensor_range.unit'
l
sensor_range
-
"S
ensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'
-
includes sensor unit: bar, PSI …; only unit part of DS-68 is writable
l
simulate_primary_value
l
simulate_secondary_value_1
l
simulate_secondary_value_2
l
device status
-
"
0: ""OK"" 13: ""non-specific error"" 17: ""Cal span too small"" 34: ""EEPROM memory fault"" 36:
""ROM
memory fault"" 37: ""RAM memory fault"" 40: ""non-specific hardware fault"" 41: ""Sensor
element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI error"" 113:
""C
ommunication hardware fault"""
l
linearization type
-
Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container
-
"
0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""
l
curve_points_1_10
-
X and Y values for the user defined linearization curve
l
curve_points_11_20
-
X and Y values for the user defined linearization curve
l
curve_points_21_30
-
X and Y values for the user defined linearization curve
l
curve_points_31_33
-
X and Y values for the user defined linearization curve
l
curve status
Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus
83
11 Supplement