1.1
95-8671
8
speciFications
OPERaTING VOLTaGE—
120-220 Vac input, 24 Vdc @ 10A output.
COMPONENTS—
EQ3001 EQP Controller
EQ3710 AIM Analog Input Module (Optional)
EQ2220 GFM Ground Fault Monitor (Included)
5.7” Human Machine Interface (HMI) - Included
24 Vdc, 10A Power Supply (Included).
TEMPERaTuRE RaNGE—
Operating: +32°F to +122°F (0°C to +50°C)
Storage: –4°F to +140°F (–20°C to +60°C).
HuMIDITY RaNGE (Instrument only)—
10 to 95% RH, non-condensing.
WEIGHT—
26.5 lb (12.0 kg) to 28.5 lb (13.0 kg), depending on
configuration.
DIMENSIONS—
24 In. (60.9 mm) x 24 In. (60.9 mm) x 6.4 In. (16.2 mm).
See Figure 1.
ENCLOSuRE—
Finish: ANSI 61 Gray
Door: 16 Gauge Steel
Body: 18 Gauge Steel.
CERTIFICaTION—
Certification of the system's components:
EQ3001 Controller
FM/CSA:
Class I, Div. 2 Groups A, B, C, D (T4)
ATEX/CE:
FM
APPROVED
®
II 3 G
Ex
nC
IIC
EN
60079-29-1
IECEx:
Ex nC IIC
EQ3710 AIM
FM/CSA:
Class I, Div. 2 Groups B, C, D (T4)
Class I, Zone 2, Group IIC (T4)
Gas Performance certified
ATEX/CE:
FM
APPROVED
®
II 3 G
Ex nA nL nC IIC
EN
60079-29-1
IECEx:
Ex nA nL nC IIC
EQ2220 GFM
FM/CSA:
Class I, Div. 2 Groups A, B, C, D (T4)
ATEX/CE:
FM
APPROVED
®
II 3 G
Ex nC IIC
IECEx:
Ex
nC
IIC
HMI
UL:
Class I, Div. 2 Groups A, B, C, D (T4)
ATEX/CE:
Ex nA nC IIC
System performance compliance in ordinary locations to:
ANSI/ISA:
12.13.01-2000, 92.0.01-1998
FM:
6310, 6320
CSA:
22.2, No. 152
ATEX/CE:
EN 60079-29-1
NOTE: When a non-certified stand alone detector is
used with the GP16XX, the output from that device is not
a certified function (when connected to AIM Module).
FM