Orientation, Calibration – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 45

Advertising
background image

I-3

95-8656

4.2

orientAtion

OPECL modules must be affixed to a solid, non-vibrating

structure capable of supporting a minimum of 100 lbs (46

kg), located within the system’s rated separation distance.

See examples below.

In all cases, the maximum movement of the supporting

structure under all anticipated operating conditions must

be no more than ±0.25 degrees. When using a vertical

post, the post should be absolutely stable and without

vibration. Generally, when the post is set into the ground,

the portion below grade should be set in concrete at least

1 meter deep.

cAlibrAtion

To initiate zero calibration of the OPECL from the

UD10-DCU Display:

1. Using the magnet to activate the switches on the

UD10-DCU display, navigate to the “Calibration”

menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Cal

Cal Gas Type
Zero Calibration
Span Cal Factor
Cal Date

Calibration

Execute
Abort

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10-DCU will display “Waiting for Zero” on

the main display screen, with a solid red LED on the

OPECL housing illuminated.

4. After the calibration is successfully completed,

the UD10-DCU automatically returns to the normal

display with the green LED illuminated on the OPECL

housing.