Det-Tronics U9500 Infiniti Gas Transmitter User Manual
Page 7
95-8444
5
10.1
1. Install the unit in a location that is best suited to cover
the area to be protected. Whenever practical, the
Infiniti should be placed where it is easily accessible
for calibration. For proper operation, sensors should
be pointing down, except for PointWatch, which must
be mounted horizontally. See Figure 1 for mounting
dimensions.
NOTE
When used with the PointWatch infrared
hydrocarbon gas detector, a 1/4 inch spacer is
required between the enclosure and the mounting
surface to allow adequate room for the detector
and calibration windshield, if required.
2. Remove the transmitter from its packing material and
note the location of the field wiring terminals and (on
the catalytic sensor transmitters only) the location of
a small sensor connection plug on the side opposite
the field wiring terminals.
3. Remove the cover from the enclosure. The transmitter
module slides into the mounting bracket within the
enclosure and all field and sensor wiring connects
to this module.
– For catalytic combustible gas transmitters, the
sensor connects to a small plug on one side of the
transmitter and all field wiring connects to terminals
on the other side.
– For all other gas transmitters, the sensor and field
wiring all connect to the terminal block on one side
of the transmitter module.
4. Connect the transmitter enclosure to the field wiring
conduit. The enclosure should be electrically
connected to earth ground.
5. Attach the sensor to the proper entry on the transmitter
enclosure. It is recommended that a layer of teflon
tape be applied to the sensor threading. Route the
wires through the entry, and tighten the sensor to the
enclosure to ensure an explosion-proof installation.
Do not overtighten.
iMPOrTanT
To ease maintenance, periodically apply
a generous amount of Lubriplate grease (part
number 102868-001) to the internal threads on the
junction box cover using an application tool. Do
not use any silicon based products, since some
materials can cause irreversible damage to the
sensing element in the gas sensor.
6. Slide the transmitter module into the bracket,
being careful to route field and sensor wires to the
appropriate location within the enclosure for easy
connection to the transmitter module. Ensure that
the transmitter display and pushbuttons (at the top)
are oriented correctly.
CaUTiOn
Wires can become pinched between the cover
and base if they are not properly tucked down
inside the enclosure.
0
DISTANCE (FEET)
2000
4000
6000
8000
10000
12 AWG
14 AWG
16 AWG
18 AWG
POWER SUPPLY VOLTAGE
32
30
28
26
24
22
20
18
16
14
A1672
Figure 3—Transmitter Wiring Requirements
for Combustible Gas Model with Relays
0
DISTANCE (FEET)
2000
4000
6000
8000
10000
12 AWG
14 AWG
16 AWG
18 AWG
POWER SUPPLY VOLTAGE
32
30
28
26
24
22
20
18
16
14
A1673
Figure 2—Transmitter Wiring Requirements
for Toxic and Oxygen Models with Relays