Operating Instructions MGB-L0...AR.-... and MGB-L0...AP.-...
11 Setup
11.1 Teach-in operation (only for MGB unicode)
The handle module must be assigned to the interlocking module using a teach-in
function before the system comprising interlocking module and handle module
forms a functional unit.
During a teach-in operation the safety outputs are switched off.
Important:
Ì
The interlocking module disables the code for the previous handle module
if teach-in is carried out for a new handle module. Teach-in is not possible
again immediately for this actuator if a new teach-in process is carried out.
The disabled code is deleted again in the interlocking module only after a
third code has been taught.
Ì
The interlocking module can only be operated with the last handle module
taught.
Ì
If, in the teach-in standby state, the interlocking module detects the handle
module taught-in or a disabled handle module, the teach-in standby state is
ended immediately and the interlocking module changes to the normal state.
Ì
If the bolt tongue is in the operating distance for less than 60 s, the handle
module is not taught. Fault display: see sections 13.2 System status table
MGB-AR, page 30 and 13.3 System status table MGB-AP, page 31.
Teaching in handle module
1. Fit handle module.
2. Close safety guard. Check for correct alignment and distance using the
marking on the interlocking module and re-adjust if necessary.
3. Insert bolt tongue in the interlocking module.
4. Apply operating voltage to the interlocking module.
¨
The green LED (State) flashes quickly (approx. 5 Hz). A self-test is performed
during this time (approx. 8 s in case of AR configuration). Teach-in operation
starts, green LED (State) flashes slowly (approx. 1 Hz). During teach-in, the
interlocking module checks whether the handle module is a disabled handle
module. Provided this is not the case, the teach-in operation is completed after
approx. 60 seconds, and the green LED (State) goes out. The new code has
now been stored, and the old code is disabled.
5. To activate the handle module's code from the teach-in operation in the inter-
locking module, the operating voltage must then be switched off at the inter-
locking module for min. 3 seconds. As an alternative, 24V can be applied to
the input RST for min. 3 seconds.
11.2 Mechanical function test
It must be possible to easily insert the bolt tongue in the interlocking module. To
check, close safety guard several times and actuate door handle.
If available, check function of the escape release. It must be possible to operate
the escape release from the inside without excessive effort (approx. 40 N).