How to wire, Model cg400, Optional activation – Hydrolevel CG400 Series User Manual

Page 2

Advertising
background image

MODEL CG400 — ALTERNATE WIRING METHOD USING PLUG CONNECTOR

HOW TO WIRE

Connect input voltage (24 VAC,
60 HZ) to terminals 1 and 2.

BURNER

POWER

SOURCE

24VAC

A

P2

P1

1

2

FACTORY
INSTALLED
JUMPER.

DO NOT
REMOVE

BURNER

COMMON

HOT

MODEL CG400

Connect terminal 2 to burner circuit
common. Connect terminal P2 to
burner Circuit in series with and
before other limit controls. Consult
boiler manufacturer instructions for
proper terminal connections.

Optional water feeder connection.
Connect feeder N to terminal 2.
Connect Feeder H to terminal 1.
Connect feeder “FEED” or “W” to
terminal A. For water feeders with
2 leads, connect feeder common
to terminal 2 and feeder hot to ter-
minal A. Note: Use of a solenoid
valve or McDonnell & Miller Model
101A water feeder may cause
flooding and is not recommended
for use with this low water cut-off.

Standing pilot boilers: Connect
“Burner” terminal to hot leg of
24VAC connection on gas valve.
Pilotless ignition boilers: Connect
“Burner” terminal to hot leg of
24VAC connection on intermittent
ignition (spark) module.
See boiler manufacturer’s
installation instructions for correct
connection to 24VAC hot.

1

BURNER

POWER

SOURCE

24VAC

+

0

LIMIT

CONTROLS

A

P2

P1

1

2

HOT

COMMON

BURNER

GAS

VALVE*

C

H

2

BURNER

POWER

SOURCE

24VAC

+

0

LIMIT

CONTROLS

A

P2

P1

1

2

GAS

VALVE*

BURNER

GAS

VALVE*

C

H

WATER

FEEDER

3

BURNER

POWER

SOURCE

24VAC

+

0

LIMIT

CONTROLS

A

P2

P1

1

2

BURNER

GAS

VALVE*

H

C

WATER

FEEDER

4

OPTIONAL
ACTIVATION

*or Intermittent Ignition

P2

2

1

A

P2

P1

1

2

BURNER

1

A

P2

P1

1

2

BURNER

WATER

FEEDER

Plug wire harness connector into matching end on circuit board.
IMPORTANT: Factory installed jumper must be in place between
terminals 1 and P1.

Optional water feeder connection. Connect feeder N to terminal 2.
Connect Feeder H to terminal 1. Connect feeder “FEED” or “W” to ter-
minal A. For water feeders with 2 leads, connect feeder common to
terminal 2 and feeder hot to terminal A. Note: Use of a solenoid valve
or McDonnell & Miller Model 101A water feeder may cause flooding
and is not recommended for use with this low water cut-off.

Standing pilot boilers: Connect “Burner” terminal to hot leg of 24VAC
connection on gas valve.

Pilotless ignition boilers: Connect “Burner” terminal to hot leg of
24VAC connection on intermittent ignition (spark) module.

See boiler manufacturer’s installation instructions for correct
connection to 24VAC hot.

2

A

P2

P1

1

2

BURNER

C H

GAS

VALVE*

WATER

FEEDER

3

*or Intermittent Ignition

OPTIONAL
ACTIVATION