6 Technical data (extract from data sheet)

36

6.7 Environmental influences

6.8 Housing

6.9 Approvals/marks of conformity

Ambient temperature range

0 to +50 °C

Ambient temperature effect

0.03 %/°C

Storage temperature range

-20 to +60 °C

Climatic conditions

 75 % relative humidity, no condensation

EMC

EN 61326-1

interference emission

Class A - only for industrial use -

immunity to interference

to industrial requirements

Housing front

zinc die-casting, optionally in stainless steel (extra code)

Housing type

housing for flush-panel mounting to IEC 61554, in stainless steel

Bezel size

144 mm × 144 mm to IEC 61554

Depth behind panel

193 mm (incl. terminals)

Panel cut-out

138

+1.0

mm × 138

+1.0

mm to IEC 61554

Panel thickness

2 to 40 mm

Housing mounting

in panel to DIN 43834

Operating position

unrestricted, but taking into account the viewing angle of the screen,
horizontally ±65°, vertically +40° to -65°

Enclosure protection

to EN 60529 Category 2, front IP65, rear IP20

Weight

approx. 3.5 kg

Mark of conformity Testing

laboratory

Certificates/
certification
numbers

Test basis

valid for

c UL us

Underwriters
Laboratories

E 201387

UL 61010-1
CAN/CSA-
C22.2 No. 61010-1

the flush-mounted
instrument; not in
conjunction with extra
code 350

II 2G Ex px IIC
II 2D Ex px IIIC IP65

electrosuisse

SEV 08 ATEX 0155 U

EN 60079-0:2009
EN 60079-2:2007
EN 61241-4:2006

the flush-mounted
instrument; only in
conjunction with
extra code 444 and
without extra code
350