Drive interface
4.2
Device commands
44
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.1
Load Lenze setting
The
= "0: Load Lenze setting" device command is used to reset the parameters of the active
application to the Lenze setting, which is stored in the controller firmware:
[4-12] "Load Lenze setting" function
• Only possible when the application has stopped and the controller is inhibited.
• All parameter changes made since the last saving of the parameter set will get lost!
• This device command only affects the settings of the operating system, application and module
parameters, the active application or the configuration selected with the function block editor
remains unchanged.
Possible status displays for this device command
Related device commands
Application 3
PS
Application 2
PS
Memory module MM
PS
9400
PS
RAM
Firmware
Application 1
Application
PS
Status (
Meaning
34050 Device command in process
0 Device command executed successfully
1 General fault
39424 CAN fault
... ...
39679 CAN fault