Flowbar iom, Step 2. install diffuser in ceiling, Step 3. secure diffuser to building structure – Titus FlowBar IOM User Manual
Page 12: Step 4. make inlet duct connections, Step 5. install ceiling tiles
12
Installation Manual - FlowBar
FlowBar IOM
Redefine your comfort zone. ™ | www.titus-hvac.com
FlowTee Installation
STEP 1. Install Hanger Clips to Diffuser
̷ Slide Upper Hanger Clips into Single Slot Diffuser rails or Upper
Support Hangers into the top bosses at each end of the Diffuser as
described in Acoustical Ceiling Installation, Step 1.
STEP 2. Install Diffuser in Ceiling
̷ Install the Diffuser on top of the ceiling grid as shown in Figure 23.
̷ The Diffuser can be positioned adjacent to a ceiling T-Bar or inside
the module.
STEP 3. Secure Diffuser to Building
Structure
̷ Secure the Diffuser to the building structure by attaching the
Hanger Brackets to the building structure with Hanger Wire.
̷ Secure the Plenums to the building structure by attaching the
Plenum tabs to the building structure with Hanger Wire.
PLENUM CLIPS
DIFFUSER
PLENUM
HOLES FOR WIRE
ATTACHMENT
(EACH END)
STEP 4. Make Inlet Duct Connections
̷ Connect the Inlet Duct to the Inlet Collar using the prescribed
methods.
STEP 5. Install Ceiling Tiles
̷ Trim and install acoustic ceiling tiles.
ModuFlow Installation
STEP 1. Install Center Tile in Diffuser
̷ Unlatch spring clips holding the back pan onto the frame and
pattern controller assembly.
̷ Cut ceiling tile to 17-15/16” x 17-15/16”.
̷ Insert the cut ceiling tile into the frame and pattern controller
assembly.
̷ Attach back pan assembly to frame making sure that the clips are
secure.
[FlowBar Moduflow]
Last edited by: TVDR
Last edited: 4-27-99
Back pan
Clips to secure
back pan
to diffuser
Ceiling Tile
ModuFlow
Diffuser
Figure 23. Installation of FlowTee Diffuser