B&D Mfg HSS User Manual

Page 6

Advertising
background image

6

PROGRAMMING OF THE B&D TEMPERATURE CONTROLLER

1. Power needs to be applied to the HSS Buffer Tank, the Temperature controller display will turn on.

2. Press and hold the MODE button for 5 seconds and it will enter programming mode. After 2 seconds the

temperature scale will show on the LCD display. By pressing the up or down button allows you to change

from “FAR” or “CEN”.

3. Press mode button once and enter the control type. The display will show “TY1”. After 2 seconds the

LCD will show “HEA” or “COL”, by pressing the up and down button allows the setting change from

“HEA” or “COL”. The setting must be “COL”.

4. Press the mode button again to change to temperature differential “SP1”. After 2 seconds the LCD will

display a number, by pressing up and down button allows the setting change the number setting.

5. Press the mode again and the LCD displays “HS1”, after 2 seconds the LCD will show current setting.

The hysteresis time, would be a built in time delay. By pressing the the up and down button to set the

desired time. Change to zero to disable.

6. Press mode button once and enter the control type. The display will show “TY2”. After 2 seconds the

LCD will show “HEA” or “COL”, by pressing the up and down button allows the setting change from

“HEA” or “COL”. The setting must be “HEA”.

7. Press the mode button again to change to temperature differential “SP2”. After 2 seconds the LCD will

display a number, by pressing up and down button allows the setting change the number setting.

8. Press the mode again and the LCD displays “HS2”, after 2 seconds the LCD will show current setting.

The hysteresis time, would be a built in time delay. By pressing the the up and down button to set the

desired time. Change to zero to disable.


The controller includes a locking function that will prevent accidental reprogramming. The soft lock is enabled
and disabled by pressing both the UP and DOWN buttons for five seconds. The LCD will show “LOC” to
indicate the controller is locked. The LCD will show “UNL” to indicate that the controller is now unlocked. The
soft lock will retain its setting through power interruptions.

Step

Annunciator

Description

Display

1

F – C

Fahrenheit or Celsius Scale

F

2

ty1

Heating or Cooling

Col or HEA

3

Sp1

Set Point Temperature

#

4

ds1

Differential Temperature

#

5

HS1

Timer for Delay

#

6

Repeat steps 2-5 for stage 2

*Note the B & D Temperature control will automatically end programming if no keys are depressed for a
period of fifteen seconds. Any settings that have been input to the control will be accepted at that point.