IS-210-5

Series LF210-5

Temperature Gas Shutoff Valves

Installation Instructions

GAS CAPACITY

C.S.A. listed ratings of this valve are:

For use with natural gas 150,000 BTU/hr.
For use with liquified petroleum gas

243,000 BTU/hr.
NOTE: See C.S.A. directory for adjust-

ment factors when used with manufac-

tured, mixed and L.P. gas-air mixtures.

Three acceptable positions for installing are

shown in sketches below. Figure 1 instal-

lation is preferred used in conjunction with

T&P relief valve.
*A pressure relief valve must be installed

as shown to prevent excess pressure by

thermal expansion. There must be no valve

between the relief valve and heater. Relief

valve must be piped to a suitable drain.

Relief valve must be located in an area that

is not subject to freezing. Removal of the

factory installed T&P valve may void

water heater manufacturer’s warranty.

DO NOT INSTALL IN THE COLD WATER LINE.
This Shutoff is an emergency device and will operate only when water temperature

approaches a maximum safe level of approximately 210°F. When it shuts off the gas to

the burner, some trouble with the operating controls is indicated. The heater installation

should be checked by a qualified service technician or licensed plumbing contractor

before being put back into service.
After operating from high temperature, the Shutoff must be manually reset (opened).

This is done by pressing on the “Reset” button, pushing it in as far as it will go (see

instructions below). Tank water temperatures must cool several degrees before valve

can be reset after operating. If, after pressing reset button, valve does not stay open

allowing gas to flow to the burner, insufficient cooling of the water is the probable

cause.
CAUTION: WHEN GAS SHUTOFF OPERATES, IT SHUTS OFF GAS SUPPLY TO

BOTH MAIN BURNER AND PILOT.
Before resetting Gas Shutoff, be sure main gas valve at the heater is shut off as well as gas

to the pilot.
After resetting Gas Shutoff Valve, proceed in lighting heater as for new installation.
This valve is not adjustable. It is factory adjusted to operate before the water temperature

exceeds 210°F.
Do not tamper with device in any way.

This Gas shutoff should be installed so that the temperature sensing element is located in the

water within the upper 6" of the tank.

Water Heaters without factory installed T&P alternate *

Fig. 3

Pressure Relief
Valve Alternate

Installation

Gas From

Supply

Cold

Drain Tube

Pressure Relief Valve

Hot

Drain Tube

Series

LF210-5

Gas To Burner

To Bottom Supply

Water Heaters equipped with T&P valve

Fig. 1

Gas From

Supply

Cold

T&P Relief Valve

Hot

Drain Tube

Series

LF210-5

Gas To Burner

LF210-5 M2

LFL210-5 M2

LFLL210-5 M2

LFLLL210-5 M2

Fig. 2

Gas From

Supply

Drain Tube

Hot

Series LF210-5

Gas To Burner

Pressure Relief Valve

Pressure Relief Valve
Alternate Installation

Water Heaters without factory installed T&P *

Cold

Drain Tube