Possible Causes:
¾
Battery temperature exceeded preset limit
¾
Faulty (worn) thermistor
Troubleshooting:
1. Press the
STOP key to revert to the IDLE screen.
2. Measure the battery tray temperature.
If an elevated battery temperature is detected, do
not re-start the charge cycle.
3. If no elevated battery temperature is detected, verify battery cable connections including the
auxiliary thermistor connections.
4. Restart the charge cycle by pressing the
START key.
5. If the fault persists, turn off the charger and contact GNB Industrial Power.
6. Battery Fault: Battery Not Detected (When Battery is Connected)
4
8
V
2
0
0
A
0
1
/
0
1
/
0
5
1
2
:
0
0
:
0
0
C
O
N
N
E
C
T
B
A
T
T
E
R
Y
D
I
S
P
L
A
Y
Possible Causes:
¾
Battery auxiliary wiring is damaged
¾
Charger auxiliary wiring is damaged
Troubleshooting:
1. Verify there is 2k-5k on the thermistor auxiliary contacts (Reading depends on battery
temperature)
2. Verify there is zero on the opposite auxiliary contacts
3. Verify there are no open connections on the charger auxiliary contacts