Pump maintenance-stand alone – Dynojet Compressed Air Air/Fuel Ratio Module User Manual

Page 24

Advertising
background image

Compressed Air Air Fuel Ratio Module Installation and User Guide

C H A P T E R 2
Air Pump Maintenance and Troubleshooting

2-8

P

UMP

M

AINTENANCE

—S

TAND

A

LONE

To ensure accurate readings, pump maintenance should be performed every six
months, or sooner, depending on usage. Periodically check the air flow and adjust as
necessary to maintain 35 L/min for each sample tube. If you are unable to adjust the
air flow to 35 L/min, clean the pump. Use a solvent to clean all pump pieces very
carefully.
1

Remove the ball valve or solenoid (for pumps using the control pod).

2

Loosen the lock nut.

3

Remove the vacuum generator exhaust port.

4

Remove the venturi body.

5

Remove the sensor(s) from the sensor block.

6

Remove the two screws securing the sensor block to the toggle clamp.

7

Use a solvent to carefully clean the vacuum generator exhaust port, venturi body,
and sensor block.
Note: Be careful not to damage the internal structure of the venturi body.

8

Install the sensor block using the two screws removed earlier.

9

Install the venturi body, vacuum generator exhaust port, and ball valve or
solenoid.

10 Install the sensor(s).
11 Replace the silicon and copper tubing if necessary.
12 Re-calibrate the pump using the flow meter. Refer to page 1-12 for more

information.

Figure 2-6: Pump Maintenance—Stand Alone Pump

lock nut

vacuum generator

exhaust port

solenoid

venturi body

sensor block

toggle clamp

silicon tube

copper sample

tube

sensor

Advertising