Configuration
33
Figure 3-7. SCALES Menu, CALIBR Submenu
See the
iQUBE
Installation Manual, PN 77224, for information about configuring
iQUBE
scales.
UNITS
LB
KG
G
OZ
TN
T
GN
TROYOZ
TROYLB
LT
CUSTOM
NONE
OFF
Specifies primary units for displayed and printed weight. Values are: LB=pound;
KG=kilogram; G=gram; OZ=ounce; TN=short ton; T=metric ton; GN=grain; TROYOZ=troy
ounce; TROYLB=troy pound; LT=long ton.
SCALES Menu, CALIBR Submenu
Parameter
Choices
Description
Level 4, CALIBR submenu
WZERO
—
Press ENTER to display and edit the zero calibration A/D count or millivolts value.
WVAL
—
Press ENTER to display and edit the test weight value.
WSPAN
—
Press ENTER to display and edit the span calibration A/D count or millivolts value.
WLIN
POINT 1 —
POINT 5
Press ENTER to display and edit test weight and calibration values for up to five linearization points.
Perform linear calibration only after WZERO and WSPAN have been set.
REZERO
—
Press ENTER to remove an offset value from the zero and span calibrations.
NOTE: Use this parameter only after WZERO and WSPAN have been set. See Section 4.2 on
page 52 for more information about using this parameter.
Table 3-5. SCALES Menu, CALIBR Submenu Parameters
SCALES Menu, FORMAT Submenu, SPLIT
≠
OFF
Parameter
Choices
Description
Table 3-4. SCALES Menu, FORMAT Submenu Parameters, SPLIT
≠
OFF (Continued)
WZERO
WVAL
WSPAN
WLIN
REZERO
POINT 4
POINT 5
POINT 1
POINT 2
POINT 3
VISIBLE
GRADS
FORMAT
CALIBR
…
…