Specifications – Smart Power Systems SSP UPS User Manual
Page 41
38
MODEL
CAPACITY
INPUT
OUTPUT
OVERLOAD
RATING
TRANSFER
TIME
BATTERY
750 / 500
SSP750
1500 / 1050
SSP1500
2000 / 1340
SSP2000
3000 / 2100
SSP3000
VA / Watt
Voltage
Voltage
Range
Acceptable
Voltage Range
Line Low
Transfer (Wide
mode)
Line High
Transfer
Frequency Range
Surge Rating ( LV/HV )
Voltage
Voltage Regulation (Batt.
Mode)
Frequency
Frequency Regulation
(Batt. Mode)
Waveform
Line Mode
Battery Mode
Typical
Backup Time (at full load)
Recharge Time
110/120/127VAC or 220/230/240VAC
0-160VAC / 0-300VAC
77/84/89VAC ± 4% or 154/161/168VAC ± 4%
132/144/152VAC ± 2% or 264/276/288VAC ± 4%
50/60Hz ±5Hz for Normal Mode; >40Hz for Generator Mode
320 / 230 Joules
110/120/127VAC or 220/230/240VAC
±5% RMS for entire battery voltage range
50Hz or 60Hz
±0.1Hz
Pure Sinewave
110% -0%, +8%; shutdown after 3 minutes. 150% -0%, +10%;
Shutdown after 10 cycles
110% ± 6%; shutdown after 30 seconds. 120 % ± 6 %;
Shutdown after 5 cycles
2-4ms Typical, 6 ms max ; 13ms max. for generator mode
500 / 640
Joules
430 / 250 Joules
5 minutes min.
3 hours to 90% after discharged
9. SPECIFICATIONS
1000 / 700
SSP1000