Table 3B — Electrical Data — Unit with Factory-Installed Motormaster® I Control

LEGEND

*Units are suitable for use on electrical systems where voltage sup-

plied to unit terminals is not below or above listed minimum and
maximum limits.

NOTE: Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

Percent Voltage Imbalance

Example: Supply voltage is 240-3-60.

AB = 243 v
BC = 236 v
AC = 238 v

Determine maximum deviation from average voltage:

(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v

Maximum deviation is 4 v. Determine percent voltage imbalance:

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT

SIZE

30GTN

UNIT

CONTROL CIRCUIT

Voltage

V-Hz (3 Ph)

Supplied*

MCA

MOCP

ICF

Rec Fuse

Size

V-Hz

(Single Ph)

Supplied

MCA and

MOCP

Min

Max

Min

Max

015

208/230-60

187

253

82.2

125

278.4

100

115-60

104

127

30

460-60

414

506

38.3

60

129.3

45

115-60

104

127

30

575-60

518

633

30.8

50

105.6

40

115-60

104

127

30

380-60

418

342

43.9

70

152.8

60

230-60

198

254

15

380/415-50

342

440

51.9

80

181.5

70

230-50

198

254

15

020

208/230-60

187

253

97.4

150

357.4

125

115-60

104

127

30

460-60

414

506

49.6

80

182.3

60

115-60

104

127

30

575-60

518

633

42.0

70

129.6

50

115-60

104

127

30

380-60

418

342

51.1

80

198.8

60

230-60

198

254

15

380/415-50

342

440

63.0

100

231.5

80

230-50

198

254

15

025

208/230-60

187

253

124.7

200

458.4

150

115-60

104

127

30

460-60

414

506

60.7

100

232.3

80

115-60

104

127

30

575-60

518

633

51.5

80

173.6

70

115-60

104

127

30

380-60

418

342

64.7

110

254.8

80

230-60

198

254

15

380/415-50

342

440

71.0

110

261.5

90

230-50

198

254

15

030

208/230-60

187

253

145.5

250

518.4

175

115-60

104

127

30

460-60

414

506

68.7

110

262.3

90

115-60

104

127

30

575-60

518

633

54.0

90

185.6

70

115-60

104

127

30

380-60

418

342

73.6

125

287.8

90

230-60

198

254

15

380/415-50

342

440

90.3

150

353.5

110

230-50

198

254

15

035

208/230-60

187

253

203.0

350

708.6

250

115-60

104

127

30

460-60

414

506

91.1

150

357.4

110

115-60

104

127

30

575-60

518

633

80.7

125

289.0

100

115-60

104

127

30

380-60

418

342

111.1

175

393.7

150

230-60

198

254

15

ICF

Maximum Instantaneous Current Flow during starting

(the point in the starting sequence where the sum of
the LRA for the starting compressor, plus the total
RLA for all running compressors, plus the total FLA for
all running fan motors is maximum).

MCA

Minimum Circuit Amps (complies with National Elec-

trical Code [NEC, U.S.A.], Section 430-24)

MOCP — Maximum Overcurrent Protection

= 100 x

max voltage deviation from average voltage

average voltage

Average voltage =

243 + 236 + 238

3

=

239 v

% Voltage Imbalance = 100 x

4

239

= 1.7%

IMPORTANT: Contact your local electric utility company
immediately if the supply voltage phase imbalance is more
than 2%.