INSTALLATION

2-6

(see Fig. 2.8). A brief description of each mode
of operation, and their requirements, is
described in the following paragraphs. Additional
information concerning field wiring is provided in
paragraphs 2.7.1 through 2.7.9. For additional
information on modes of operation, refer to
Chapter 5.

Figure 2.8

I/O Box Terminal Location

2.6.1 CONSTANT SETPOINT MODE
The Constant Setpoint Mode is used when it is
desired to have a fixed setpoint that does not
deviate. No wiring connections other than
electrical supply connections are required for
this mode. However, if desired, fault monitoring
or enable/disable interlock wiring can be utilized
(see paragraphs 2.7.9.1 and 2.7.10).

2.6.2 INDOOR/OUTDOOR RESET MODE

This mode of operation increases supply water
temperature as outdoor temperatures decrease.
An outside air temperature sensor (AERCO PN
122790) is required. The sensor MUST BE
wired to the I/O Box wiring terminals (see Fig.
2.9). For more information concerning the
outside air sensor installation, refer to paragraph
2.7.1









mA OUT

RS-485
COMM.

+

-

+
-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+
-

+
-

AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY
120 VAC, 5A, RES

AUX RELAY
120 VAC, 5A, RES

G

RELAY CONTACTS:
120 VAC, 30 VDC
5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC
COM
NO

NC
COM
NO

NOT USED

Figure 2.9 I/O Box Terminal Strip