SAFETY DEVICE TESTING

6-6

of closure switches. The proof of closure switch

circuit is checked as follows:
1. Set the unit’s

ON/OFF switch to the OFF

position.

2. Place the unit in Manual Mode and set the

valve position between 25% and 30%

3. Refer to Figure 6-1 and locate downstream

SSOV #1(natural gas).

4. Remove the cover from SSOV #1 by

loosening the screw shown in Figure 6-4. Lift

off the cover to access the terminal wiring

connections.

5. Disconnect wire #148 from SSOV #1 to

“open” the proof of closure switch circuit.

When wire #148 is disconnected, it opens

the proof of closure switch circuit for both

the natural gas and propane downstream

SSOVs.

6. The unit should fault and display SSOV

SWITCH OPEN.

7. Replace wire #148 and press the

CLEAR

button.

8. Set the

ON/OFF switch to ON to start the

unit.

9. Remove the wire again when the unit

reaches the purge cycle and PURGING is

displayed.

10. The unit should shut down and display

SSOV FAULT DURING PURGE.

11. Replace the wire on SSOV #1 and press the

CLEAR button. The unit should restart.

ACTUATOR

COVER

SCREW

SSOV #1

ACTUATOR

COVER

Figure 6-4

SSOV #1 Actuator Cover Location

6.12 PURGE SWITCH OPEN DURING

PURGE

The Purge Switch (and Ignition Switch) is

located on the Air/Fuel Valve. To check the

switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the

OFF

position. Place the unit in manual mode and

set the fire rate between 25% and 30%.

2. Remove the Air/Fuel Valve cover by rotating

the cover counterclockwise to unlock it and

then lift up (see Figure 6-5).

3. Remove one of the two wires (#171 or #172)

from the Purge Switch (Figure 6-6).

4. Initiate a unit start sequence.
5. The unit should begin it’s start sequence,

then shut down and display PRG SWITCH

OPEN DURING PURGE.

6. Replace the wire on the Purge Switch and

depress

the CLEAR button. The unit should

restart.

6.13 IGNITION SWITCH OPEN DURING

IGNITION

The Ignition Switch (and the Purge Switch) is

located on the Air/Fuel Valve. To check the

switch, proceed as follows:
1. Set the unit’s

ON/OFF switch to the OFF

position.

2. Place the unit in Manual Mode and set the

valve position between 25% and 30%.

3. Remove the Air/Fuel Valve cover (Figure

6-5) by rotating the cover counterclockwise

to unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170)

from the Ignition Switch (Figure 6-6).

5. Initiate a unit start sequence.
6. The unit should begin it’s start sequence

and then shut down and display IGN

SWITCH OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and

press the

CLEAR button. The unit should

restart.