Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 67 of 210

GF-133

Ph.: 800-526-0288

03/20/14

Figure 4-4: TAC Valve Adjust (Idle Screw)


4.5 REASSEMBLY AFTER COMBUSTION CALIBRATION

Once the combustion calibration adjustments are properly set, the unit can be reassembled for
service operation.

Reassembly

1. Set the ON/OFF switch in the OFF position.

2. Disconnect AC power from the unit.

3. Shut off the gas supply to the unit.

4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable

pipe thread compound.

5. Remove the combustion analyzer probe from the 1/4” vent hole in the exhaust manifold.

Replace the 1/8” NPT plug in the manifold.

6. Replace all previously removed sheet metal enclosures on the unit.

TAC VALVE

IDLE SCREW