8 combustion air, 1 combustion air from outside the building, 2 combustion air from inside the building – AERCO KC1000 Low NOx Water Heater July 2011 User Manual

Page 17: Note, Installation

Advertising
background image

INSTALLATION

2-9

2.7 FLUE GAS VENT INSTALLATION

AERCO Gas Fired Venting and Combustion Air

Guide, GF-1050, must be consulted before any

flue or combustion air venting is designed or

installed. Suitable, U/L approved, positive pres-

sure, watertight vent materials MUST be used

for safety and UL certification. Because the unit

is capable of discharging low temperature

exhaust gases, the flue must be pitched back

towards the unit a minimum of 1/4" per foot to

avoid any condensate pooling and to allow for

proper drainage.

While there is a positive flue pressure during

operation, the combined pressure drop of vent

and combustion air systems must not exceed

140 equivalent feet of 0.81” W.C. Fittings as

well as pipe lengths must be calculated as part

of the equivalent length. For a natural draft

installation the draft must not exceed - 0.25”

W.C. These factors must be planned into the

vent installation. If the maximum allowable

equivalent lengths of piping are exceeded, the

unit will not operate properly or reliably.

For Massachusetts installations, the Heatfab

Division of the Selkirk Corporation provides vent

systems which conform to all applicable

requirements for installations within the

Commonwealth of Massachusetts. Contact

information for this supplier is as follows:

Selkirk Corporation

Heatfab Division

130 Industrial Blvd.

Turners Falls, MA 01376

Phone: 1-800-772-0739

www.heat-fab.com

2.8 COMBUSTION AIR

The AERCO Gas-Fired Heater Venting and

Combustion Air Guide, GF-1050 MUST be

consulted before any flue or inlet air venting is

designed or installed. Air supply is a direct

requirement of ANSI 223.1, NFPA-54, CSA

B149.1 and local codes. These codes should be

consulted before a permanent design is

determined.

The combustion air must be free of chlorine,

halogenated hydrocarbons or other chemicals

that can become hazardous when used in gas-

fired equipment. Common sources of these

compounds are swimming pools, degreasing

compounds, plastic processing, and refrigerants.

Whenever the environment contains these types

of chemicals, combustion air MUST be supplied

from a clean area outdoors for the protection

and longevity of the equipment and warranty

validation.

The more common methods of combustion air

supply are outlined in the following paragraphs.

For combustion air supply from ducting, consult

the AERCO GF-1050, Gas Fired Venting and

Combustion Air Guide.

2.8.1 COMBUSTION AIR FROM OUTSIDE

THE BUILDING

Air supplied from outside the building must be

provided through two permanent openings. For

each unit these two openings must have a free

area of not less than one square inch for each

4000 BTUs input of the equipment or 250

square inches of free area. The free area must

take into account restrictions such as louvers

and bird screens. For Canada installations, refer

to the requirements specified in CSA B149.1-10,

8.4.1 and 8.4.3.

2.8.2 COMBUSTION AIR FROM INSIDE

THE BUILDING

When combustion air is provided from within the

building, it must be supplied through two

permanent openings in an interior wall. Each

opening must have a free area of not less than

one square inch per 1000 BTUH of total input or

1000 square inches of free area. The free area

must take into account any restrictions, such as

louvers.

NOTE

KC1000 units equipped with Low NOx

Burners require an optional Cold Air

Damper for operation with Direct

Vent/Sealed Combustion. The Cold Air

Damper is also required when the unit is

installed in an area where the combustion

air supply temperature can drop below

55°F. Refer to the following paragraph

(2.8.3) and GF-1050 for installation details

2.8.3 SEALED COMBUSTION

The KC Heater is UL approved for 100% sealed

combustion application when installed properly.

When a sealed combustion air application is

installed, the sealed combustion air piping must

be deducted from the maximum allowable

discharge piping amounts. Each unit must have

a minimum 6" diameter connection made to the

special Inlet Air Adapter # GP-18917 available

from AERCO. This adapter bolts directly on to

the air inlet of the unit’s blower. See installation

instructions with adapter. All inlet air ducts must

be sealed air tight.

Advertising