Proper burner flame, High altitude burner orificing, Blocked vent shut-off system – Louisville Tin and Stove WOW253 User Manual

Page 13

Advertising
background image

NATURAL GAS

WOW253

1.3

5 5

5 6

5 6

5 7

WOW403

5 4

5 5

5 5

5 6

5 6

L.P. GAS

WOW254

6 7

6 8

6 9

7 0

7 0

WOW404

6 6

6 8

6 8

6 9

7 0

MODEL

0 to

2,000’

4,000’

6,000’

8,000’ -

NO.

2,000’

4,000’

6,000’

8,000’

10,000’

PROPER BURNER FLAME

Appliance input ratings are based on sea level operation and need not be changed for operation up to 2,000 (609.9m)
elevation. For operation at elevations above 2,000 ft. (609.9m), manufactured to specified deration conditions for
Canada and the United States, use the following orifice chart for/to determine the correct orifice DMS for a specific
elevation.

Page 13

SPECIFIC ELEVATIONS

HIGH ALTITUDE BURNER

ORIFICING

Appliance input ratings are based on sea level operation
and need not be changed for operation up to 2,000 ft.
(609.9m) elevation. For operation at elevations bove 2,000
ft. (609.9m), manufactured to specified deration condi-
tions for Canada and the United States. Use the follow-
ing orifice chart for/to determine the correct orifice DMS
for a specific elevation.

BLOCKED VENT SHUT-OFF

SYSTEM

This heater is equipped with a blocked vent shut-
off system that will automatically turn the heater
off in the advent of the vent exhaust or air intake
pipe becoming blocked. This blockage may be
caused by snow accumulation, insects, small ani-
mals, animal nest, etc.
Once this occurs the heater will remain in a lock-
out cycle for one hour. After one hour there will
be an ignition attempt. If the blockage has been
removed, the heater will return to normal opera-
tion. If the blockage remains, the heater will re-
turn to a one hour lock out cycle.
If this problem occurs, homeowners must not at-
tempt to operate or repair the heater themselves
but contact a qualfied service agency.

There is no primary air adjustment on the burner and with correct installation, a proper flame is assured; since the
correct manifold pressure and orificing has been done at the factory for elevations up to 2,000 ft.

FIGURE 14

LIGHT BLUE OUTER MANTLE

DARKER BLUE INNER MANTLE

FIGURE 13 - - WOW403 / WOW404

BURNER
BOX

GAS
VALVE

SIGHT
GLASS

SIGHT GLASS

BURNER
BOX

MANIFOLD

FIGURE 13 - - WOW253 / WOW254

After conversion is complete, attach P/N 91137 Label
adjacent to the rating plate.