FloAire FastWrap XL Commercial Kitchen Grease Duct Enclosure System User Manual

Fastwrap® xl

Advertising
background image

Product Data & Installation Guide
1. Product Description

FireMaster® FastWrap XL is a flexible blanket composed of
high temperature fibers classified for applications to 2192°F
(1200°C) and fully encapsulated in a durable glass fiber rein-
forced foil facing for easy handling and installation. FastWrap
XL is UL Classified and ULC Listed in various systems for 1
and 2 hour fire resistive enclosure protection, reduced clear-
ance for kitchen exhaust ducts, electrical circuit protection, and
as a component in various UL firestop designs for fire resist-
ance rated floors, ceilings, and walls. The core fibers in
FastWrap XL are manufactured using Thermal Ceramics
patented Superwool® fiber which is an alkaline-earth silicate
wool with low biopersistence and therefore increased safety for
installers. FastWrap XL is under UL’s Follow-Up Service
Program to ensure the consistent quality essential to this life-
safety application.
Product Features

• Zero clearance to combustibles at any location
• Thin and Lightweight at 1-1/2” (38mm) thick, 6 pcf (96 kg/m

3

)

density

• Contours easily to complex duct designs
• Optimized installation with inside layer butt joints on grease

duct enclosures per ASTM E 2336

• Fully foil encapsulated for fast and clean installation
• Completely inorganic and non-combustible
• Contains 2192°F (1200°C) rated fibers for added safety

margin

• Wide variety of through penetration firestop systems
• Resistant to mold growth
• Good sound absorption

2. Applications

• 1 and 2 hour enclosure and firestop system for kitchen

exhaust ducts

• Zero clearance from enclosure to combustibles for kitchen

exhaust ducts

• 1 and 2 hour enclosure and firestop system for hazardous

exhaust ducts, pressurization ducts, clothes dryer exhaust
ducts, trash and linen chutes, and other fire rated HVAC
ducts

• 1 hour circuit integrity protection for cable trays and steel

conduits

• Engineered solutions and tested systems for fire protection

of structural steel beams and columns, and storage vessels
per ASTM E119, ISO 834, and UL1709

3. Physical Characteristics

4. Performance Specifications

5. Listings/Building Code Reports

FastWrap® XL

Commercial Kitchen Grease Duct Enclosure System

Air Ventilation Duct Enclosure System

Product

Unit Size

Units/

Ctn.

Wt./

Ctn.

FastWrap XL

Roll 1-1/2” x 24" x 25'

1

37.5 lbs.

FastWrap XL

Roll 1-1/2” x 48" x 25'

1

75 lbs.

FastWrap XL Collar Roll 1-1/2” x 6" x 25'

4

37.5 lbs.

Color

White blanket with silver foil encapsulation

Reference Standard

Standard No.

Performance

Grease Duct Enclosure System ASTM E2336

Pass

Section 16.1 -

Non-Combustibility

ASTM E136

Pass

Section 16.2-Fire Resistance

(wall)

ASTM E119

Pass

Section 16.3 - Durability Test

ASTM C518

Pass

Section 16.4 - Internal Fire Test ASTM E2336

Pass

Section 16.5 - Fire Engulfment

(duct)

ASTM E814/E119 Pass

ULC Grease Duct Test Protocol

Pass

Grease Duct Clearances

UL 1978

Pass

Air Ventilation Duct Enclosure ISO 6944

Pass

Surface Burning Characteristics

Flame Spread (foil/blanket)

ASTM E84

5/0

Smoke Developed (foil/blanket) ASTM E84

10/0

Thermal Resistance

(R-value @ 70°F)

ASTM C518

7.3 per layer

Mold Growth

(75% -95% humidity)

ASTM D6329

Resistant

* Laboratory Listings per UL 1978 have been withdrawn.

Listed Uses

Agency Listing

Layers

Grease Duct Enclosure per ASTM

E2336 and AC101

UL

G18

2

ICC-ES ESR 2213

Grease Duct Insulation per ULC

Grease Duct Insulation Test Protocol ULC

FRD 4, 7

2

Through Penetration FireStop

System per ASTM E814, UL 1479

UL

See Figure 2 1 or 2

ULC

Ventilation Duct Enclosure System

per ISO 6944-1985

UL

HNLJ.V1, 2,

3, 4, 11, 12,

19

1

ULC

FRD 3, 5, 6,

18

Electrical Circuit Protective System

UL

FHIT.5

2

* International Code Council - Engieering Service

Advertising