Interlogix 584509-W User Manual

Introduction, Mounting location

Advertising
background image

P/N 11089

• REV H • OCT12

1

Wireless ShatterPro Acoustic Sensor Installation
Instructions

Introduction

This is the Wireless ShatterPro Acoustic Sensor

Installation Instructions for models 584503-W (3 V) and

584509-W (9 V). The sensor is designed to detect breaking

glass from framed windows in the perimeter of a building.

Install the sensor on a perimeter loop armed whenever the

door and window contacts are armed. Avoid 24-hour loop

applications where the sensor is armed all day and all night.

The false-alarm technology will be pushed to its limit in a 24-

hour loop.

The sensor’s false-alarm immunity is best in rooms with only
moderate noise. Some sounds can duplicate the points on the

glassbreak pattern the sensor detects.

The sensor may not consistently detect cracks in glass, or

bullets which break through the glass. Glassbreak sensors

should always be complemented with interior protection.

Connect the sensor to a UL listed control panel, or a power

supply that provides at least four hours of standby power.

Use a 9-volt battery if longer life is needed in the 584509 -W.

Mounting location

The sensor must always be in direct line of sight of all windows

to be protected. The sensor cannot consistently detect glass

breaking around corners or in other rooms. There is no

required front, back, up or down orientation.

Wall mount

The best wall-mount location is on the opposite wall, assuming
the glass to be protected is within the sensor’s range and line

of sight. The adjoining wall can also be used.

Ceiling mount

Mount the sensor in a location that is in direct line of sight of

the glass to be protected. However, since sound travels

directionally out from a broken window, a position 8 ft. (2.4 m)

into the room provides better detection.

Use the following guidelines to determine the best mounting

location:

Mount the sensor at least 3.3 ft. (1 m) from the windows

being protected and at least 4 ft. (1.2 m) from noise

sources such as TVs, speakers, sinks, and doors.

Mount the sensor in the direct line of sight of the glas s to

be protected.

Avoid rooms smaller than 10 x 10 ft. (3m x 3m).

Avoid locations where lined, insulating, or sound-

deadening drapes or closed wooden shutters are used.

Mount the sensor in a suitable environment: temperature

between 0 and 120°F (-18 and 50°C); and humidity

between 10 and 90% noncondensing. Do not install the

sensor in humid rooms. Excess moisture on the circuit

board can eventually cause a short and a false alarm.

Mount the sensor on a stable surface up to 25 ft. (7.6 m)

from the farthest point on the glass surface.

Avoid locations that expose the sensor to possible false -

alarm sources such as:

glass airlocks and vestibule areas;

kitchens;

corner mounting;

residential car garages;

small utility rooms;

stairwells;

bathrooms; and

small acoustically live rooms.

Coverage range

The sensor is omni-directional, providing 360° coverage.

Coverage is measured from the sensor to the point on the

glass farthest from the sensor. The sensor can be mounted as

close as 3.3 ft. (1 m) from the glass. The maximum range

depends on the type of glass being protected:

Armor-coated glass

Mount sensor no more than 12 ft. (3.6 m) from the glass.

Advertising
This manual is related to the following products: