MT2P Pool Heater
Page 5
Figure 1. Dimensional Data.
AIR
VENT
SHIPPING
UNIT
CONN.
CONN.
WEIGHT
1
SIZE
A
B
C
D
E
F
W
V
LBS kG
500
33¾ 85
16¾ 43
6½ 17
10 25
8 20
46¼ 117 6 15
8 20
425 193
750
45¾ 116
22¾ 53
6½ 17
10 25
9½ 24
58¼ 148 6 15
10 25
505 229
1000
57¾ 147
28¾ 73
6½ 17
10 25
9½ 24
70¼ 178 8 20
10 25
615 279
1250
68¼ 173
34
87
10¼
26
10 25
9 23
80¾ 205 8 20
12 30
675 306
1500
78¾ 200
39½ 100
10¼
26
10 25
9 23
91¼ 232 8 20
12 30
760 345
1750
89¼ 227
44¾ 113
10¼
26
10 25
9 23
101¾ 258
8 20
12 30
825 375
2000
99¾ 253
49¾ 127
10¼
26
10 25
9 23
112¼ 285 12 30
14 36
955 434
NOTES: 1. Add 55 lbs (25kg) for pump-mounted units.
Dimensions in
inches cm.
in the appliance has/have sufficient power to pull air
and vent properly when the following guidelines for
horizontal air and vent are followed (
see Table 1
).
NOTE: On all MT2P models, the vent collar size is
larger than the size of the vent pipe that can be used.
Side wall vent terminals for these sizes are shipped
with replacement vent collars, to accommodate
horizontal vent sizes. Vent collar size and horizontal
pipe diameters can be found in Table 1. The larger vent
collar size is to accommodate Category I (vertical) vent
systems.
NOTE: When located on the same wall, the MT2P
combustion air intake terminal must be installed a
minimum of 12" (30cm) below the exhaust vent terminal
and separated by a minimum of 36 inches (91cm)
horizontally.
The air intake terminal must be installed high enough
to avoid blockage from snow, leaves and other debris.
Never obtain combustion air from the pool area. Corrosion
of and/or damage to the pool heater may result.