LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual
Page 91
Page 87
N
eo
T
herm
Boilers and Water heaters
237
Invalid DHW (Domestic Hot
Water) connector type setting
L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
238
Invalid Stack connector type
setting
L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
239
Invalid Header connector type
setting
L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
240
Invalid Outdoor connector type
setting
L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Code Description
L or H Procedure